Commercial Garage Door Insulation: R-Value, U-Factor and Model Comparison
For commercial garage door insulation, compare a properly scoped door U-factor and stated air-infiltration result first, then use section R-value and foam type as supporting details. Lower U-factor and air infiltration are better; higher R-value is better. Do not invert a section R-value to estimate the complete door's U-factor. Match the exact model, size, glazing, seals, configuration and test basis.
Uptime Dock & Door Research · Last verified September 19, 2026 · Dataset v1.0 · 40 source-linked configurations from 7 manufacturers
Download the CSV · Download the JSON · Download the data dictionary · Print the quote checklist
Scroll horizontally to view all columns.
| Term | What it means here | Better direction |
|---|---|---|
| R-value | Resistance to heat flow for the material, section, slat or other scope named by the source, in h·ft²·°F/Btu | Higher, when scope is comparable |
| U-factor | Heat transmission through the tested or stated door scope, in Btu/(h·ft²·°F) | Lower, when scope is comparable |
| Air infiltration | Air passing through or around the tested assembly under the source's stated conditions, usually in cfm/ft² | Lower, under comparable test conditions |
Evidence labels used on this page: ★ Source-reported means checked in the linked official source. ● Calculated means computed from source-linked inputs with the method shown. Manufacturer figures remain manufacturer-stated unless the source expressly identifies a separate test or verification program.
Commercial garage door insulation comparison: 40 source-linked configurations
The fastest way to compare commercial garage door insulation is to put the model, door family, insulation material, R-value scope, U-factor scope and air test in the same place. A mixed list sorted by one large number hides the differences that matter.
What the reviewed dataset shows
- ● Calculated: This release contains 40 named model or configuration records from 7 manufacturers, checked on the row-level dates in the download.
- ● Calculated: The dataset includes 36 sectional-door rows, 2 full-view or aluminum rows and 2 rolling-door rows. Door families stay separate because their constructions and published rating scopes are not interchangeable.
- ● Calculated: The reviewed sectional-door rows with numeric values span published R-values of not stated in the reviewed rows and published U-factors of not stated in the reviewed rows. Those are ranges in this reviewed sample, not boundaries for the entire market.
- ● Calculated within one manufacturer: The reviewed Clopay polystyrene rows span published R-values of not stated in the reviewed rows and U-factors of not stated in the reviewed rows. The reviewed Clopay polyurethane rows span published R-values of not stated in the reviewed rows and U-factors of not stated in the reviewed rows. This controls for manufacturer better than a market-wide comparison, but it still does not prove that foam type alone caused every difference.
- ★ Source-reported: The worked Amarr Model 2743 example below publishes R-— and U-—. Its reciprocal section-R calculation is —, which is not the published door U-factor.
- ★ Source-reported: Overhead Door publishes air-infiltration values of 0.08 cfm/ft² for Model 591; 0.13 for Models 592, 596 and 599; and 0.46 for Model 598 on the named product pages: Model 591, Model 592, Model 596, Model 598, and Model 599. The values retain the test conditions stated by each source; they are not one family-wide figure.
Scroll horizontally to view all columns.
| Manufacturer | Model or configuration | Door family | Insulation | Published R-value | Published U-factor | Air infiltration | Source |
|---|---|---|---|---|---|---|---|
| Overhead Door | Aluminum Full View — 521 — insulated glass | Full-view aluminum | Insulated glass | — | — | — | Official source |
| Overhead Door | Aluminum Full View — 521 — low-E insulated glass | Full-view aluminum | Low-E insulated glass | — | — | — | Official source |
| Cornell | Thermiser Max — ESD30 | Rolling steel | Closed-cell foamed-in-place urethane | — | — | 0.3 cfm/ft² | Official source |
| Cornell | Thermiser Max Low U — ESD40 | Rolling steel | Premium insulated slat system | — | — | — | Official source |
| Amarr | Amarr 2432 — 2432 | Sectional steel | Polystyrene | — | — | — | Official source |
| Amarr | Amarr 2732 — 2732 | Sectional steel | Polystyrene | — | — | — | Official source |
| Amarr | Amarr 2742 — 2742 | Sectional steel | Polyurethane | — | — | — | Official source |
| Amarr | Amarr 2743 — 2743 | Sectional steel | Polyurethane | — | — | — | Official source |
| C.H.I. Overhead Doors | Insulated Sandwich — 3206 | Sectional steel | Polyurethane | — | — | — | Official source |
| Clopay | Energy Series — 3150 | Sectional steel | Polystyrene | — | — | — | Official source |
| Clopay | Energy Series — 3154 | Sectional steel | Polystyrene | — | — | — | Official source |
| Clopay | Energy Series — 3155 | Sectional steel | Polystyrene | — | — | — | Official source |
| Clopay | Energy Series — 3200 | Sectional steel | Polystyrene | — | — | — | Official source |
| Clopay | Energy Series — 3211 | Sectional steel | Polystyrene | — | — | — | Official source |
| Clopay | Energy Series — 3213 | Sectional steel | Polystyrene | — | — | — | Official source |
| Clopay | Energy Series — 3220 | Sectional steel | Polystyrene | — | — | — | Official source |
| Clopay | Energy Series with Intellicore — 3715 | Sectional steel | Polyurethane | — | — | — | Official source |
| Clopay | Energy Series with Intellicore — 3717 | Sectional steel | Polyurethane | — | — | — | Official source |
| Clopay | Energy Series with Intellicore — 3718 | Sectional steel | Polyurethane | — | — | — | Official source |
| Clopay | Energy Series with Intellicore — 3720 | Sectional steel | Polyurethane | — | — | — | Official source |
| Clopay | Energy Series with Intellicore — 3721 | Sectional steel | Polyurethane | — | — | — | Official source |
| Clopay | Energy Series with Intellicore — 3722 | Sectional steel | Polyurethane | — | — | — | Official source |
| Clopay | Energy Series with Intellicore — 3723 | Sectional steel | Polyurethane | — | — | — | Official source |
| Clopay | Energy Series with Intellicore — 3724 | Sectional steel | Polyurethane | — | — | — | Official source |
| Clopay | Energy Series with Intellicore — 3730 | Sectional steel | Polyurethane | — | — | — | Official source |
| Overhead Door | Insulated Steel-Back — 470 | Sectional steel | Polystyrene | — | — | — | Official source |
| Overhead Door | Thermacore Advanced Performance — 850 | Sectional steel | Polyurethane | — | — | 0.21 cfm/ft² | Official source |
| Overhead Door | Thermacore Sectional Steel — 591 | Sectional steel | Polyurethane | — | — | 0.08 cfm/ft²<br><small>Manufacturer-stated test condition; see linked model page</small> | Official source |
| Overhead Door | Thermacore Sectional Steel — 592 | Sectional steel | Polyurethane | — | — | 0.13 cfm/ft²<br><small>Manufacturer-stated test condition; see linked model page</small> | Official source |
| Overhead Door | Thermacore Sectional Steel — 593 | Sectional steel | Polyurethane | — | — | — | Official source |
| Overhead Door | Thermacore Sectional Steel — 594 | Sectional steel | Polyurethane | — | — | — | Official source |
| Overhead Door | Thermacore Sectional Steel — 596 | Sectional steel | Polyurethane | — | — | 0.13 cfm/ft²<br><small>Manufacturer-stated test condition; see linked model page</small> | Official source |
| Overhead Door | Thermacore Sectional Steel — 598 | Sectional steel | Polyurethane | — | — | 0.46 cfm/ft²<br><small>Manufacturer-stated test condition; see linked model page</small> | Official source |
| Overhead Door | Thermacore Sectional Steel — 599 | Sectional steel | Polyurethane | — | — | 0.13 cfm/ft²<br><small>Manufacturer-stated test condition; see linked model page</small> | Official source |
| Overhead Door | WindStorm — 515 | Sectional steel | Polyurethane | — | — | — | Official source |
| Overhead Door | WindStorm — 525 | Sectional steel | Polyurethane | — | — | — | Official source |
| Raynor | ThermaSeal — TM175 | Sectional steel | Polyurethane | — | — | 0.22 cfm/ft² | Official source |
| Raynor | ThermaSeal — TM200C | Sectional steel | Polyurethane | — | — | — | Official source |
| Raynor | ThermaSeal — TM300 | Sectional steel | Polyurethane | — | — | — | Official source |
| Wayne Dalton | ThermoMark — 530 | Sectional steel | Polyurethane | — | — | 0.21 cfm/ft² | Official source |
Overhead Door — Aluminum Full View — 521 — insulated glass
- Door family
- Full-view aluminum
- Insulation
- Insulated glass
- R-value
- Not stated in reviewed source
Calculated door section R-value - U-factor
- Not stated in reviewed source
Independently tested and verified per ANSI/DASMA 105 - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Overhead Door — Aluminum Full View — 521 — low-E insulated glass
- Door family
- Full-view aluminum
- Insulation
- Low-E insulated glass
- R-value
- Not stated in reviewed source
Calculated door section R-value - U-factor
- Not stated in reviewed source
Independently tested and verified per ANSI/DASMA 105 - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Cornell — Thermiser Max — ESD30
- Door family
- Rolling steel
- Insulation
- Closed-cell foamed-in-place urethane
- R-value
- Not stated in reviewed source
Slat R-value calculated using ASHRAE Handbook of Fundamentals - U-factor
- Not stated in reviewed source
Manufacturer-published complete-door U-factor - Air infiltration
- 0.3
Not stated in reviewed source
Official source
Checked 2026-09-19
Cornell — Thermiser Max Low U — ESD40
- Door family
- Rolling steel
- Insulation
- Premium insulated slat system
- R-value
- Not stated in reviewed source
Not stated in reviewed source - U-factor
- Not stated in reviewed source
Independently verified assembly U-factor - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Amarr — Amarr 2432 — 2432
- Door family
- Sectional steel
- Insulation
- Polystyrene
- R-value
- Not stated in reviewed source
Manufacturer-published R-value; exact calculation basis not stated in visible table - U-factor
- Not stated in reviewed source
Manufacturer-published U-factor; exact test basis not stated in visible table - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Amarr — Amarr 2732 — 2732
- Door family
- Sectional steel
- Insulation
- Polystyrene
- R-value
- Not stated in reviewed source
Manufacturer-published R-value; exact calculation basis not stated in visible table - U-factor
- Not stated in reviewed source
Manufacturer-published U-factor; exact test basis not stated in visible table - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Amarr — Amarr 2742 — 2742
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Manufacturer-published R-value; exact calculation basis not stated in visible table - U-factor
- Not stated in reviewed source
Manufacturer-published U-factor; exact test basis not stated in visible table - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Amarr — Amarr 2743 — 2743
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Manufacturer-published R-value; exact calculation basis not stated in visible table - U-factor
- Not stated in reviewed source
Manufacturer-published U-factor; exact test basis not stated in visible table - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
C.H.I. Overhead Doors — Insulated Sandwich — 3206
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Manufacturer-published R-value; exact calculation basis not stated on visible page - U-factor
- Not stated in reviewed source
Manufacturer-published U-factor; exact test basis not stated on visible page - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Clopay — Energy Series — 3150
- Door family
- Sectional steel
- Insulation
- Polystyrene
- R-value
- Not stated in reviewed source
Calculated door section R-value per DASMA TDS-163 - U-factor
- Not stated in reviewed source
Tested door U-factor per ANSI/DASMA 105 - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Clopay — Energy Series — 3154
- Door family
- Sectional steel
- Insulation
- Polystyrene
- R-value
- Not stated in reviewed source
Calculated door section R-value per DASMA TDS-163 - U-factor
- Not stated in reviewed source
Tested door U-factor per ANSI/DASMA 105 - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Clopay — Energy Series — 3155
- Door family
- Sectional steel
- Insulation
- Polystyrene
- R-value
- Not stated in reviewed source
Calculated door section R-value per DASMA TDS-163 - U-factor
- Not stated in reviewed source
Tested door U-factor per ANSI/DASMA 105 - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Clopay — Energy Series — 3200
- Door family
- Sectional steel
- Insulation
- Polystyrene
- R-value
- Not stated in reviewed source
Calculated door section R-value per DASMA TDS-163 - U-factor
- Not stated in reviewed source
Tested door U-factor per ANSI/DASMA 105 - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Clopay — Energy Series — 3211
- Door family
- Sectional steel
- Insulation
- Polystyrene
- R-value
- Not stated in reviewed source
Calculated door section R-value per DASMA TDS-163 - U-factor
- Not stated in reviewed source
Tested door U-factor per ANSI/DASMA 105 - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Clopay — Energy Series — 3213
- Door family
- Sectional steel
- Insulation
- Polystyrene
- R-value
- Not stated in reviewed source
Calculated door section R-value per DASMA TDS-163 - U-factor
- Not stated in reviewed source
Tested door U-factor per ANSI/DASMA 105 - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Clopay — Energy Series — 3220
- Door family
- Sectional steel
- Insulation
- Polystyrene
- R-value
- Not stated in reviewed source
Calculated door section R-value per DASMA TDS-163 - U-factor
- Not stated in reviewed source
Tested door U-factor per ANSI/DASMA 105 - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Clopay — Energy Series with Intellicore — 3715
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Calculated door section R-value per DASMA TDS-163 - U-factor
- Not stated in reviewed source
Tested door U-factor per ANSI/DASMA 105 - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Clopay — Energy Series with Intellicore — 3717
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Calculated door section R-value per DASMA TDS-163 - U-factor
- Not stated in reviewed source
Tested door U-factor per ANSI/DASMA 105 - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Clopay — Energy Series with Intellicore — 3718
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Calculated door section R-value per DASMA TDS-163 - U-factor
- Not stated in reviewed source
Tested door U-factor per ANSI/DASMA 105 - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Clopay — Energy Series with Intellicore — 3720
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Calculated door section R-value per DASMA TDS-163 - U-factor
- Not stated in reviewed source
Tested door U-factor per ANSI/DASMA 105 - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Clopay — Energy Series with Intellicore — 3721
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Calculated door section R-value per DASMA TDS-163 - U-factor
- Not stated in reviewed source
Tested door U-factor per ANSI/DASMA 105 - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Clopay — Energy Series with Intellicore — 3722
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Calculated door section R-value per DASMA TDS-163 - U-factor
- Not stated in reviewed source
Tested door U-factor per ANSI/DASMA 105 - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Clopay — Energy Series with Intellicore — 3723
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Calculated door section R-value per DASMA TDS-163 - U-factor
- Not stated in reviewed source
Tested door U-factor per ANSI/DASMA 105 - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Clopay — Energy Series with Intellicore — 3724
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Calculated door section R-value per DASMA TDS-163 - U-factor
- Not stated in reviewed source
Tested door U-factor per ANSI/DASMA 105 - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Clopay — Energy Series with Intellicore — 3730
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Calculated door section R-value per DASMA TDS-163 - U-factor
- Not stated in reviewed source
Tested door U-factor per ANSI/DASMA 105 - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Overhead Door — Insulated Steel-Back — 470
- Door family
- Sectional steel
- Insulation
- Polystyrene
- R-value
- Not stated in reviewed source
Calculated door section R-value - U-factor
- Not stated in reviewed source
Independently tested and verified per ANSI/DASMA 105 - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Overhead Door — WindStorm — 515
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Calculated door section R-value - U-factor
- Not stated in reviewed source
Independently tested and verified per ANSI/DASMA 105 - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Overhead Door — WindStorm — 525
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Calculated door section R-value - U-factor
- Not stated in reviewed source
Independently tested and verified per ANSI/DASMA 105 - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Overhead Door — Thermacore Sectional Steel — 591
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Calculated door section R-value - U-factor
- Not stated in reviewed source
Independently tested and verified per ANSI/DASMA 105 - Air infiltration
- 0.08
Manufacturer-stated test condition; see linked model page
Official source
Checked 2026-09-19
Overhead Door — Thermacore Sectional Steel — 592
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Calculated door section R-value - U-factor
- Not stated in reviewed source
Independently tested and verified per ANSI/DASMA 105 - Air infiltration
- 0.13
Manufacturer-stated test condition; see linked model page
Official source
Checked 2026-09-19
Overhead Door — Thermacore Sectional Steel — 593
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Calculated door section R-value - U-factor
- Not stated in reviewed source
Independently tested and verified per ANSI/DASMA 105 - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Overhead Door — Thermacore Sectional Steel — 594
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Calculated door section R-value - U-factor
- Not stated in reviewed source
Independently tested and verified per ANSI/DASMA 105 - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Overhead Door — Thermacore Sectional Steel — 596
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Calculated door section R-value - U-factor
- Not stated in reviewed source
Independently tested and verified per ANSI/DASMA 105 - Air infiltration
- 0.13
Manufacturer-stated test condition; see linked model page
Official source
Checked 2026-09-19
Overhead Door — Thermacore Sectional Steel — 598
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Calculated door section R-value - U-factor
- Not stated in reviewed source
Independently tested and verified per ANSI/DASMA 105 - Air infiltration
- 0.46
Manufacturer-stated test condition; see linked model page
Official source
Checked 2026-09-19
Overhead Door — Thermacore Sectional Steel — 599
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Calculated door section R-value - U-factor
- Not stated in reviewed source
Independently tested and verified per ANSI/DASMA 105 - Air infiltration
- 0.13
Manufacturer-stated test condition; see linked model page
Official source
Checked 2026-09-19
Overhead Door — Thermacore Advanced Performance — 850
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Calculated door section R-value - U-factor
- Not stated in reviewed source
Independently tested and verified per ANSI/DASMA 105 - Air infiltration
- 0.21
Not stated in reviewed source
Official source
Checked 2026-09-19
Raynor — ThermaSeal — TM175
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Calculated R-value - U-factor
- Not stated in reviewed source
Tested U-factor; manufacturer states TPV verification - Air infiltration
- 0.22
Not stated in reviewed source
Official source
Checked 2026-09-19
Raynor — ThermaSeal — TM200C
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Calculated R-value - U-factor
- Not stated in reviewed source
Tested U-factor; manufacturer states TPV verification - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Raynor — ThermaSeal — TM300
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Calculated R-value - U-factor
- Not stated in reviewed source
Tested U-factor; manufacturer states TPV verification - Air infiltration
- Not stated in reviewed source
Not stated in reviewed source
Official source
Checked 2026-09-19
Wayne Dalton — ThermoMark — 530
- Door family
- Sectional steel
- Insulation
- Polyurethane
- R-value
- Not stated in reviewed source
Calculated door section R-value - U-factor
- Not stated in reviewed source
Independently tested and verified per ANSI/DASMA 105 using solid doors and specific sizes - Air infiltration
- 0.21
Not stated in reviewed source
Official source
Checked 2026-09-19
Source: Official manufacturer-controlled pages linked in each row. Compiled by Uptime Dock & Door Research for Commercial Door Thermal Performance Benchmark v1.0. Release and page audit: September 19, 2026. A dash means the reviewed source did not state that field; it never means zero.
How to use the table
- Compare rows within the same door family first.
- Read the small scope line under every R-value and U-factor.
- Open the official source before putting a number into a specification or article.
- Treat a blank as unknown, not as zero.
- Ask whether the quoted size, glazing, pass door, vent, track and seal package match the published configuration.
- Use the downloadable CSV or JSON when you need every field, including dimensions, thermal-break wording, checked date and notes.
R-value vs U-factor: which number should you compare?
Use a properly scoped door U-factor to understand heat transmission through the tested or stated door configuration. Use section R-value to understand the manufacturer's stated resistance for the section, slat, insulation or other named component. Do not treat the two as reciprocal whole-door ratings.
The Door & Access Systems Manufacturers Association's R-value and U-factor explanation says a door-section R-value does not establish the complete door's thermal performance and cannot simply be inverted to obtain the U-factor for the whole assembly. DASMA's standards index lists ANSI/DASMA 105-2017 as the test method for thermal transmittance and air infiltration of garage doors.
What commercial garage door R-value measures
R-value is resistance to heat flow. A higher number means more resistance for the scope being rated. On a commercial-door page, that scope may be the insulation, the door section, a slat or another named construction.
That is why the words beside the number matter. A section R-value does not automatically include every joint, perimeter condition, piece of glazing, pass door, vent or installed opening detail.
What commercial garage door U-factor measures
U-factor describes heat transmission through the tested or stated scope. A lower number means less heat transmission. Building codes often express assembly requirements as U-factors, but a manufacturer value still needs its test method, specimen and configuration attached.
A U-factor without those details is not ready to compare with another quote.
Why U-factor is not simply 1 divided by an advertised section R-value
The arithmetic works only when R and U describe the same complete scope. An advertised section R-value and a published door U-factor often do not.
Scroll horizontally to view all columns.
| Amarr Model 2743 example | Value |
|---|---|
| Manufacturer-published R-value | — |
Mathematical reciprocal, 1 ÷ — | — |
| Manufacturer-published U-factor | — |
Source: Amarr Model 2743 official product page, checked September 19, 2026. The R-value and U-factor are source-reported; the reciprocal is Uptime's calculation from the published R-value.
The reciprocal is not the published U-factor because the two ratings do not represent an identical thermal scope. Do not use 1 ÷ section R-value as a substitute for a complete-door U-factor.
Why the rating label matters as much as the number
A manufacturer may publish more than one thermal figure for a product in different contexts. A comparison table, an individual product page and a project submittal may describe different specimens, options or scopes.
The correct response is not to pick the most favorable number. Record the exact source, test basis, specimen or configuration and document revision, then ask which value applies to the quoted door.
Where air infiltration fits
U-factor addresses heat transmission through the stated door scope. Air infiltration addresses air passing through or around the tested assembly under stated pressure conditions. A well-insulated section does not by itself prove that the installed opening is well sealed.
Compare air values only when the unit and test condition are the same or demonstrably comparable. Do not turn a missing air value into zero. Perimeter seals, section joints, glazing, installation and door condition all affect the opening a facility actually operates.
Scroll horizontally to view all columns.
| Claim on a quote | What to ask for |
|---|---|
| “R-18 insulated door” | R-value of what: foam, section, slat or another stated scope? |
| “U-0.17” | Which test method, specimen, size and option package? |
| “Low air leakage” | What value, unit, test pressure and configuration? |
| “Thermally broken” | Which section joints, stiles, framing parts or other heat paths are interrupted? |
| “Meets energy code” | Which jurisdiction, adopted edition, section, climate zone and exact door configuration? |
Source: Questions are Uptime's editorial checklist, built from the rating distinctions described by DASMA and the fields manufacturers publish in the linked benchmark sources.
What insulation rating should you specify for a commercial garage door?
There is no universal best R-value for every commercial opening. Start with whether the opening is part of a conditioned building envelope and what the adopted code, project documents, owner requirements and exact door configuration require. Then compare U-factor, air infiltration, section R-value, glazing, seals, size and operating conditions.
Is the opening in the conditioned thermal envelope?
Start with the building, not a product badge:
- Is the area intentionally heated or cooled?
- Does the door separate conditioned space from outdoors or an unconditioned space?
- Is it a loading bay, drive-in door, service bay, fire-station bay, cooler boundary or unconditioned storage opening?
- Does the operation need stable temperature or humidity?
- Do the design documents identify the opening as part of the thermal envelope?
A warehouse, service bay and temperature-sensitive room can have different requirements even when the openings look similar.
What does the project actually require?
Ask for the items that can be verified:
- Governing jurisdiction and adopted code edition
- Project specification and energy-model assumptions
- Required assembly U-factor
- Required air-infiltration performance
- Climate zone used by the project
- Exact door dimensions
- Glazing percentage and glass type
- Pass door, louver, vent or exhaust-port configuration
- Wind, cycle, fire, security and operator requirements as separate criteria
Do not replace a project requirement with an unsourced “recommended R-value” chart.
How often will the door be open?
A closed-door thermal rating describes the closed assembly under stated conditions. It does not measure the heat carried through an opening while the door is open or quantify a site's annual energy use.
For a frequently open bay, closed-door U-factor still matters, but it is only one part of the operating problem. Door-open time, traffic flow, controls and the appropriate door family are separate decisions.
Is condensation or thermal bow part of the problem?
More insulation does not by itself settle a condensation or thermal-bow question. Indoor humidity, outdoor temperature, surface temperature, air movement, color, solar exposure, construction and door condition can all matter.
DASMA lists separate technical data sheets for condensation and thermal bow in its technical data sheet index. Use the exact door manufacturer's instructions and the project designer's criteria for a real condition.
Scroll horizontally to view all columns.
| Opening condition | What to prioritize |
|---|---|
| Unconditioned building with no project thermal criterion | Durability, weather protection and stated project requirements; do not buy by R-value alone |
| Conditioned warehouse or service bay | Properly scoped U-factor, air infiltration, seals, exact dimensions and options |
| Temperature-sensitive operation | Project-specific envelope and operating criteria |
| Door with substantial glazing | The exact glazed configuration, not a solid-panel rating |
| High-use opening | Closed-door rating plus door-open time, traffic and suitable operating system |
| Retrofit proposal | Added weight, balance, operator compatibility, manufacturer instructions and the absence of an assumed tested U-factor |
Source: This is an editorial decision framework. It does not establish code compliance or replace a project specification.
Polyurethane vs polystyrene: what does the reviewed data show?
In the reviewed Clopay model tables, polyurethane configurations carry higher published section R-values and generally lower published U-factors than the reviewed polystyrene configurations. That does not prove that insulation material alone determines complete-door performance. Thickness, section construction, joints, steel skins, glazing, size, seals and test configuration also matter.
Scroll horizontally to view all columns.
| Reviewed Clopay subset | Published R-value range | Published U-factor range |
|---|---|---|
| Polystyrene rows | not stated in the reviewed rows | not stated in the reviewed rows |
| Polyurethane rows | not stated in the reviewed rows | not stated in the reviewed rows |
Source: Uptime calculation from the current Clopay polystyrene model table and Clopay polyurethane model table included in Dataset v1.0. Missing numeric values are excluded from each range.
What the construction names mean
Polystyrene is commonly used as a rigid insulating material in named commercial-door sections. Polyurethane is commonly foamed between skins in named sandwich-panel products. The exact construction belongs to the model documentation; the material name alone does not describe every joint, skin, reinforcement or option.
What this comparison does not prove
The table does not establish:
- Universal ranges for every manufacturer
- That insulation material alone caused the difference
- Annual energy savings or payback
- Condensation resistance
- Structural superiority
- That every polyurethane door outperforms every polystyrene door on every criterion
- That the largest R-value is the right door for the project
Which material should you choose?
Begin with the project's U-factor and air-infiltration requirements. Confirm the exact named model and options. Then compare gauge, dimensions, tracks, cycle requirements, glazing, wind, controls, warranty and installed scope separately. Foam type is one decision input, not the whole decision.
What else changes a commercial door's thermal performance?
The insulated section is only one part of the closed opening. Section joints, perimeter seals, glazing, thermal bridges, pass doors, vents, dimensions, installation and the test configuration can change what the published number represents and how the installed opening performs.
Section joints and thermal breaks
A thermal bridge is a conductive path that lets heat bypass insulation. A thermal break interrupts or reduces that path in the part named by the manufacturer.
“Thermally broken” is not a complete rating. Ask which joints, stiles, frames or other parts the statement covers and whether the quoted configuration matches the source.
Header, jamb and bottom seals
Header, jamb and bottom seals control air paths around the perimeter. A torn seal, visible gap, damaged section or door that no longer sits correctly is a condition problem, not a reason to assign the section a different R-value.
For safe observations and stop-use conditions, use the commercial garage door troubleshooting reference.
Windows and full-view sections
Do not assign a solid-section rating to a glazed configuration unless the manufacturer states that the rating applies. Request the exact glass, frame, percentage and complete quoted configuration.
Full-view aluminum rows remain separate in the dataset because their construction and published thermal metrics are not equivalent to a solid insulated sectional door.
Pass doors, vents, louvers and exhaust ports
Options alter the construction. Ask whether the published R-value, U-factor and air result include the selected pass door, louver, vent or exhaust port. Do not estimate the change unless the manufacturer publishes it for that configuration.
Door size and test specimen
A maximum available size is not necessarily the test-specimen size. Larger doors can require different reinforcement, hardware or options. Do not assume that every manufacturer's published U-factor uses one universal 10-by-10-foot specimen. Record the specimen and test basis actually stated in the source or submittal.
Installation and adjustment
The installed opening must align, travel and seal as intended. Do not improvise spring, cable, track, operator-force, electrical or interlock work to chase an insulation problem.
Stop using a door with uncontrolled movement, broken support hardware, a hanging cable, a displaced track, a damaged section that affects travel or another condition the manufacturer identifies as unsafe. Use trained, authorized personnel and equipment-specific procedures.
What do codes and standards actually require?
A test standard explains how a characteristic is determined. A model code states requirements that a jurisdiction may adopt and amend. A manufacturer submittal describes the named product and configuration. Uptime's checklist helps a buyer compare evidence. Those are different documents with different jobs.
Scroll horizontally to view all columns.
| Source | Type | What it does | What it does not prove |
|---|---|---|---|
| ANSI/DASMA 105-2017 | Test method listed by DASMA | Addresses thermal transmittance and air infiltration of garage doors | Does not set every project's required U-factor |
| DASMA TDS #163 | Technical data sheet listed by DASMA | Addresses U-factor and R-value terminology for residential and commercial garage doors | Is not an adopted local energy code |
| DASMA TDS #176 | Technical data sheet listed by DASMA | Addresses adding weight to a garage-door assembly | Is not permission to alter a specific door |
| DASMA TDS #196 | Technical data sheet listed by DASMA | Addresses U-factor and the DASMA Thermal Performance Verification Program | Does not make unlike product claims identical in scope |
| International Energy Conservation Code | Model code | Supplies provisions that jurisdictions may adopt and amend | Is not automatically the law in every location |
| Manufacturer submittal | Product-specific document | States the quoted model, options and published performance | Does not set the jurisdiction's requirement |
| Uptime quote checklist | Editorial tool | Helps a reader request comparable evidence | Is not a code, standard, test, certification or engineering approval |
Source: DASMA standards index, DASMA technical data sheet index and the official International Code Council code library. The table paraphrases public titles and functions; it does not reproduce protected standards text.
A narrow 2021 IECC sectional-door example
Section C402.4.5.2 of the 2021 International Energy Conservation Code addresses a specifically defined opaque nonswinging-door configuration: a horizontally hinged sectional door with a single row of fenestration occupying 14% to 25% of the door area. For that defined configuration, the model-code text states an assembly U-factor no greater than 0.440 in Climate Zones 0 through 6 and 0.360 in Climate Zones 7 and 8.
Source: 2021 IECC, Section C402.4.5.2, International Code Council.
That is not a national requirement for every commercial garage door. It is one model-code edition, one clause and one defined configuration. A real project must use the edition and amendments adopted by the authority having jurisdiction, the correct climate zone and the provision that applies to the exact opening.
How to verify a requirement for a real project
- Identify the authority having jurisdiction.
- Identify the adopted code edition and local amendments.
- Confirm the project's climate zone and thermal-envelope classification.
- Read the provision that applies to the actual door and glazing configuration.
- Compare the requirement with the exact quoted model, options and test basis.
- Keep the current submittal with the project record.
Can you add insulation to an existing commercial garage door?
Some doors can accept manufacturer-approved insulation or another documented modification, but a generic insulation layer should not be assumed to create a tested complete-door U-factor. Added material also changes door weight, which can affect the counterbalance system, operator, hardware and safe operation.
Scroll horizontally to view all columns.
| Question | Factory-insulated named model | Field-added material |
|---|---|---|
| Published model R-value or U-factor | May be available for the named configuration | Do not infer a complete-door value from the material alone |
| Weight included in door design | Part of the documented configuration | Must be evaluated for the existing door |
| Section construction | Defined by the manufacturer | Existing door remains the base assembly |
| Test scope | May have a named method, specimen or verification basis | Do not assume a complete-door test |
| Buyer action | Verify the current model submittal | Identify the door and obtain manufacturer-qualified review |
Source: Editorial comparison grounded in the measurement distinctions above and DASMA's listed TDS #176, “Adding Weight To a Garage Door Assembly”. This page does not reproduce or replace equipment-specific instructions.
What to verify before a modification
- Manufacturer and exact model
- Door label or serial information
- Width, height and section construction
- Existing insulation and skin configuration
- Counterbalance system
- Operator and controls
- Proposed material and total added weight
- Manufacturer instructions or approved kit documentation
- Qualified commercial-door assessment
Do not use this page for spring turns, cable work, counterbalance changes, operator-force changes, track modification, electrical work, interlock bypasses or improvised attachment near moving hardware.
How to compare two insulated commercial-door quotes or submittals
Two insulation claims are comparable only when you know what each number measures and whether the quoted model, dimensions, options and test basis match the project.
Printable 12-point quote checklist
- Manufacturer and exact model — Record the product line, model, configuration and document revision.
- Door family — Sectional steel, full-view aluminum, rolling steel or another named family.
- Opening and door dimensions — Width, height, track or lift arrangement and unusual clearances.
- Section or slat construction — Layers, materials, thickness, steel gauges and interior backing.
- Insulation material — Polyurethane, polystyrene, insulated glass, insulated slat system or another named material.
- Published R-value and scope — Material, section, slat or other stated scope; include the source's calculation or test reference.
- Published U-factor and scope — Test method, specimen or configuration and whether it applies to the quoted door.
- Air-infiltration value — Number, unit, test method and pressure or wind-speed condition.
- Thermal breaks and seals — Section joints, stiles, header, jamb, bottom and other specified seals.
- Openings and options — Glass, full-view sections, pass door, louvers, vents, exhaust ports and hardware changes.
- Code and project criteria — Jurisdiction, adopted edition, climate zone, required U-factor or leakage and design specification.
- Separate nonthermal requirements — Wind pressure, cycles, impact, fire rating, security, operator, controls, warranty and installation scope.
Worked example: why there is no one-number winner
Scroll horizontally to view all columns.
| Criterion | Amarr Model 2743 | Overhead Door Model 850 |
|---|---|---|
| Published section R-value in the reviewed source | — | — |
| Published U-factor in the reviewed source | — | — |
| Overall winner from these two numbers alone | Not determinable | Not determinable |
Sources: Amarr Model 2743 and Overhead Door's U-factor and R-value table, checked September 19, 2026. Values are manufacturer-published for the scopes stated by those sources.
One row may have the higher section R-value while another has the lower published U-factor. That still does not establish an overall winner. The rating scope, air infiltration, dimensions, glazing, structural requirements, duty cycle, controls and project criteria must match the actual job.
Common commercial garage door insulation mistakes
Ranking doors only by advertised R-value
A large section R-value does not describe every thermal path or installed-opening condition.
Calculating complete-door U-factor as 1 divided by section R-value
That calculation fails when the two values describe different scopes.
Mixing sectional, full-view and rolling-door rows
Keep unlike door families separate unless the project has already established a comparable performance basis.
Treating missing air data as zero leakage
A blank means the reviewed source did not state a value. It is not a zero.
Ignoring windows, pass doors, vents and seals
Request the value for the exact quoted configuration.
Accepting “meets code” without a code citation
Ask for the jurisdiction, adopted edition, section, climate zone and configuration.
Treating a dealer copy as the primary product source
Trace a product claim to the manufacturer-controlled page or current submittal whenever one is available.
Adding retrofit insulation without reviewing weight
Identify the system and obtain manufacturer-qualified review before changing a counterbalanced door assembly.
Assuming more insulation solves an operational problem
Door-open time, damage, sealing, condensation and door-family selection can be separate problems.
Methodology
Uptime compiled this benchmark from manufacturer-controlled U.S. product and rating pages. Each row keeps the source's stated metric and scope. Unlike door families stay separate. Missing fields remain unknown, and absent ratings are not estimated.
Inclusion criteria
A record needed:
- A manufacturer-controlled source URL
- A named commercial model or configuration
- At least one published thermal-performance value
- Enough context to identify the door family
- A source-checked date or a correction date recorded in the row
Exclusion criteria
This release excludes:
- Dealer copies when an official manufacturer source was available
- Residential-only configurations
- High-speed fabric-door rows that would change the page's commercial-garage-door job
- Untraceable “typical” ranges
- Search snippets without a supporting source page
- Rows marked as placeholders or needing verification
- Annual energy-savings or payback estimates
- Duplicate model/configuration/source records
How the values were handled
- No conversion was made between published R-value and published U-factor.
- Missing numeric values remain blank in CSV and
nullin JSON. - Air values measured under different stated conditions were not normalized.
- Manufacturer wording was retained in the scope fields.
- The table does not assign a best model.
- Product data are manufacturer-stated; Uptime did not perform laboratory testing or certify products.
Calculated findings
- Record count:
COUNT(records) - Manufacturer count:
COUNT(DISTINCT manufacturer) - Ranges:
MIN(value)throughMAX(value)after numeric conversion, with blanks excluded - Reciprocal example:
1 ÷ published section R-value, shown only to demonstrate why unlike scopes cannot be substituted
Evidence categories
- ★ Source-reported: Checked in the linked official source.
- ● Calculated: Computed from source-linked inputs with the formula or filter described.
- Editorial guidance: A decision or checklist built from the verified evidence; not a code provision, product certification or engineering approval.
Version history
Scroll horizontally to view all columns.
| Version | Release and verification date | Change |
|---|---|---|
| 1.0 | September 19, 2026 | Initial publication-ready release; corrected model-level air-infiltration values, removed unverified placeholder rows and retained row-level source scope |
Limitations
- This is a curated reviewed dataset, not a census of every commercial door sold in the United States.
- Product values are manufacturer-published. Uptime did not perform laboratory or field testing.
- A rating may apply to a defined specimen or option set rather than every available size.
- Product pages, options and document revisions can change after the checked date.
- Missing values are unknown, not zero.
- Different test scopes can prevent direct numerical comparison.
- The dataset does not establish local code compliance.
- It does not estimate annual energy savings, utility cost or payback.
- It does not rank wind, cycles, impact, fire rating, security, maintenance, warranty or installed cost.
- It is not an approved product submittal, engineering approval or substitute for current project documents.
- No open-data license is asserted. Manufacturer names and source-reported facts remain attributable to their original sources.
Sources
Standards, code and technical guidance
- DASMA standards index — ANSI/DASMA 105 title and edition as listed by the issuer.
- DASMA technical data sheet index — public titles and subject boundaries for TDS #163, #176, #195 and #196.
- The Difference Between R-Value and U-Factor — DASMA explanation of section R-value and complete-door U-factor.
- 2021 IECC, Chapter 4 CE — official model-code text for the scoped C402.4.5.2 example.
Manufacturer sources
Every product row links to its manufacturer-controlled source. The downloadable source register groups those URLs with the records they support and their checked dates.
Download the commercial-door insulation data
- Commercial Door Thermal Performance Benchmark v1.0 — CSV
- Commercial Door Thermal Performance Benchmark v1.0 — JSON
- Data dictionary — CSV
- Source register — CSV
- Chart input — JSON
The downloads contain manufacturer-stated model data and Uptime's source and scope fields. They are research and comparison files, not approved product submittals.
How to cite this dataset
Uptime Dock & Door Research. Commercial Door Thermal Performance Benchmark v1.0. Uptime Dock & Door, September 19, 2026.
/research/commercial-garage-door-insulation/.
Include the version, access date and CSV or JSON filename when citing a specific download. Cite the linked manufacturer or issuer when the sentence depends on one product value, test method or code clause.
Related research and next steps
- Compare commercial garage door cost and quote scope.
- Compare rolling steel and sectional doors.
- Use the commercial garage door troubleshooting reference for damage, unusual movement or a door that no longer seals normally.
- A damaged, binding or poorly sealing door may need assessment rather than another insulation layer. Review commercial garage and overhead door service options when the next task is repair or replacement service.
Questions people ask
Is a lower U-factor better for a commercial garage door?
Yes. A lower U-factor means less heat transmission for the stated test scope. Confirm that the values being compared describe equivalent specimens and configurations.
What is a good R-value for a commercial garage door?
There is no universal number. The project depends on the conditioned envelope, adopted requirements, U-factor, air infiltration, glazing, seals, dimensions and operating conditions.
Does an insulated commercial door stop drafts?
Not automatically. Section insulation and air infiltration are different performance questions. Perimeter seals, joints, alignment, damage and installation also matter.
Do windows reduce commercial-door insulation performance?
Windows change the construction and can change the applicable thermal value. Request the rating for the exact glazed configuration instead of applying a solid-panel value.
Can an existing commercial garage door be insulated?
Some systems may accept a manufacturer-approved modification, but added weight and the absence of an assumed tested complete-door rating must be addressed before alteration.
Publisher note: Uptime Dock & Door Research is the research and reference section of uptimedockanddoor.com. Its methods, independence and correction process are described in the editorial policy. Its methods, independence and correction process are described in the editorial policy. It compiles source-based material for facilities, warehouse, safety, purchasing and reporting work. Uptime Dock & Door is an independent commercial service-referral publisher, not a manufacturer, standards body, government agency, laboratory or repair contractor.