Skip to main content
UPTIME DOCK & DOORKeep Every Bay Moving.

Commercial Garage Door Wind Load Requirements: What the Code Asks For and What Proves It

A commercial garage door’s wind requirement is a project-specific positive and negative design pressure in pounds per square foot (psf), not a universal miles-per-hour (mph) rating. The locally adopted code and the project design criteria establish those pressures. The exact door assembly then needs matching test, label, drawing, attachment, and—where required—impact or regional approval evidence.

Uptime Dock & Door Research · Last verified September 2026 · Primary sources rechecked 19 September 2026 · Dataset version 1.1.0

Uptime Dock & Door Research is the research and reference section of uptimedockanddoor.com, an independent commercial service-referral publisher. We are not a manufacturer, a laboratory, a standards body, a building department, an engineering firm, or a repair contractor. See our About page and editorial policy.


What we found

Ten findings, most useful first. ★ Source-reported means we checked the statement in the cited primary document. ● Calculated means we computed it from cited inputs and show the method.

  1. ★ There is no single nationwide commercial-door mph or psf requirement. The International Building Code (IBC) is a model code that jurisdictions adopt and may amend. The project’s adopted code, the applicable edition of the American Society of Civil Engineers’ ASCE 7 structural-load standard, site and building inputs, opening, and pressure basis establish the requirement. (ICC, International Building Code overview; ASCE Hazard Tool)
  2. ★ Both pressure directions matter. The 2024 IBC model-code provision for garage and rolling doors calls for a permanent label that includes the positive and negative design wind pressure rating. One unsigned psf number is not a complete match. (2024 IBC §1709.5.2.1)
  3. ★ The widely repeated 9.6 psf number is not a universal floor for every project. The Door & Access Systems Manufacturers Association (DASMA) Technical Data Sheet (TDS) 155y calls 9.6 psf the minimum value charted inside that guide’s stated assumptions. DASMA separately notes that non-rated doors are available where wind-load requirements are not in force. (DASMA TDS 155y; DASMA TDS 1502)
  4. ★ Exposure category can move the guide value sharply. In DASMA’s ASCE 7-22 guide, Exposure C multipliers are 1.49 at a 15 ft mean roof height and 1.44 at 25 ft; Exposure D multipliers are 1.81 and 1.73. These are guide-specific multipliers, not a substitute for the project calculation. (DASMA TDS 155y)
  5. ● The paired DASMA guide values changed little between the two editions we compared. Across 428 matched scenario-direction rows in TDS 155v and TDS 155y, the largest absolute change was 0.5 psf and the largest percentage change outside rows pinned at the shared 9.6 psf chart floor was 1.90%. That does not mean the wind speed at a real address stayed the same. (Method and downloads)
  6. ★ The five model-code label fields are explicit. The 2024 IBC names the manufacturer, model or series, positive and negative design pressure, installation-drawing reference, and applicable test standard. (2024 IBC §1709.5.2.1)
  7. ★ The 1.5× test load is code, not a second door rating. The 2024 IBC says each covered assembly is tested for 10 seconds at 1.5 times design pressure. A door’s usable design-pressure rating is not automatically that higher test pressure. (2024 IBC §1709.5.2)
  8. ★ The label alone is not proof of the installed assembly. DASMA’s inspection guidance tells the reader to compare the label with the exact wind-load drawing and then check the configured components and attachment path. (DASMA TDS 181)
  9. ★ The door rating does not prove the wall can carry the reactions. The tracks or guides, brackets, anchors, jambs, framing, and building structure complete the load path and need their own project evidence. (DASMA TDS 168; DASMA TDS 181)
  10. ★ A static wind rating does not tell you whether the door can operate in wind. DASMA described operational wind load as a separate question and reported work toward a test method; its current standards index does not list a separately titled operational-wind test standard. (DASMA standards; Door + Access Systems, Summer 2025 Tech Corner)

On this page


Does my building actually need a wind-rated door?

The answer depends on the code and amendments adopted for the project, the scope of the work, the opening, and the authority having jurisdiction (AHJ)—usually the building department or other enforcing authority. Many exterior commercial-door projects need documented wind resistance. It is not accurate to say that every commercial door in every U.S. building must carry the same minimum rating—or that a door with no wind label is automatically unlawful everywhere.

The International Building Code is a model code. A governmental jurisdiction adopts an edition, may amend it, and decides how it applies to new construction, replacement, repair, and alteration. The newest IBC or ASCE 7 edition does not automatically govern a project. (ICC, International Building Code overview)

The current ASCE Hazard Tool lets a user select ASCE 7-10, ASCE 7-16, or ASCE 7-22 and retrieve site-specific hazard data. That tool helps establish inputs. It does not select or approve a door. (ASCE Hazard Tool)

What the 9.6 psf number really means

DASMA’s TDS 155y shows selected garage- and commercial-door pressure scenarios under ASCE 7-22 and the 2024 IBC. Its notes call 9.6 psf the minimum value charted. That is a boundary inside that guide, not a national declaration that every commercial door must be rated to at least 9.6 psf.

The distinction matters because:

  • The guide has stated building, height, opening, topography, enclosure, roof-slope, and wall-zone assumptions.
  • Openings outside those assumptions need a project-specific determination.
  • A jurisdiction may use another adopted edition or amendment.
  • A replacement or repair may follow an existing-building or local permitting path.
  • DASMA’s label guidance acknowledges that non-rated doors exist where a wind-load requirement is not in force.

Sources: DASMA TDS 155y, general notes; DASMA TDS 1502.

What changes from one project to another

The project requirement can change with all of these:

Scroll horizontally to view all columns.

Project wind-load inputs and where to record them
InputWhy it mattersWhere the project should record it
Project address and jurisdictionEstablishes the authority having jurisdiction, adopted code, amendments, and site hazard lookupCode analysis, permit record, structural criteria
ASCE 7 editionDetermines the wind procedure and data set being usedStructural design criteria
Risk category and building useCan change mapped wind criteria and additional checksStructural criteria or code analysis
Basic design wind speed and basisSupplies a site hazard input, not the finished door ratingHazard report or sealed criteria
Exposure categoryRepresents surrounding terrain and changes velocity pressureStructural criteria or calculation
Topographic and special-region factorsCan change site effects beyond a simple map valueSealed calculation or AHJ criteria
Mean roof heightAffects pressureDrawings or calculation
Building dimensions and roof slopeAffect the pressure method and whether a guide appliesPlans or calculation
Enclosure classificationAffects internal pressureStructural criteria
Opening width, height, and wall locationAffect the assembly and components-and-cladding pressureDoor schedule and elevation
Effective wind area or pressure zoneHelps determine the external pressure coefficientPressure schedule or calculation
Positive and negative pressure basisEstablishes the two values the door rating must meetProject pressure schedule

Sources: DASMA TDS 155y; DASMA TDS 168; ASCE Hazard Tool.

What about replacing a door in an existing building?

The building department decides which adopted-code and existing-building provisions apply to the work. An insurer or customer may also impose a separate evidence requirement.

Do not assume that “same size” means “same requirement,” and do not assume that every replacement triggers a full new-construction path. Before ordering, identify:

  1. The project jurisdiction and permit path.
  2. The pressure requirement that will be used.
  3. Whether the existing jambs, header, wall, and anchors are being reused.
  4. Whether impact or a special product-approval program applies.
  5. Which documents the reviewer or insurer expects.

DASMA’s FAQ says retrofit questions belong with the authority having jurisdiction and notes that an insurer may have its own mitigation requirements. (DASMA TDS 168)


Who decides the number, and what is it made of?

The project design process or building official establishes the required design pressure and its inputs. A door manufacturer or supplier can use confirmed project information to select a product, but should not invent the project’s exposure, code edition, pressure basis, or supporting-wall design.

DASMA assigns the exposure-category determination to the design professional or building official because it depends on the actual site. Manufacturer selection tools can be useful for preliminary selection, but DASMA itself says calculated values are preliminary and final responsibility lies with a registered design professional. (DASMA TDS 193; DASMA Technical Data Sheets)

Who owns which decision

Scroll horizontally to view all columns.

Wind-load decisions, owners and buyer evidence
DecisionTypical ownerEvidence the buyer should receive
Adopted code, amendments, and permit pathAuthority having jurisdiction and project code analysisNamed edition, amendment, permit or review record
Site wind data and ASCE 7 editionProject structural design processHazard report or structural criteria
Exposure, risk category, enclosure, and pressure zonesDesign professional or building officialProject calculation or criteria
Required positive and negative design pressureProject design professional or accepted project documentsPressure schedule with units and basis
Door model, size, configuration, and labeled capacityManufacturer or supplier using confirmed inputsProduct data, label fields, test/evaluation evidence
Exact installation configurationManufacturer drawing and installerDrawing number/revision and installed-condition record
Jambs, header, wall, anchors, and building-side reactionsProject structural design and responsible construction partiesAccepted structural detail and manufacturer reactions
Permit, product-program, or insurance acceptanceAHJ or named programApproval, inspection, certificate, or closeout record

Sources: DASMA TDS 168, TDS 181, and TDS 193. The table organizes the source responsibilities into one workflow.

The eleven inputs behind one pressure number

DASMA’s current ASCE 7-22 guide identifies basic wind speed, exposure category, the allowable-stress load factor, mean roof height, door location on the building, wind directionality, topographic effects, ground elevation, roof pitch, enclosure category, and door area as inputs behind the published values. (DASMA TDS 155y)

Two details often surprise buyers:

  • Where the opening sits on the wall matters. The published guides have a stated end-zone-overlap limit. A wider opening or different corner condition can put the project outside the chart.
  • The compass direction on the plan is not the same as a pressure-zone decision. DASMA’s FAQ says the method accounts for wind toward and away from the door; the project wall location and pressure zone still matter. (DASMA TDS 168)

The one question to ask first

What is the required design pressure for this opening, positive and negative, in psf—and what pressure basis and code edition were used?

Ask for the answer in writing. Every downstream check—the quote, label, drawing, report, installation, and approval—depends on it.


Why is a “150 mph door” not enough?

A wind-speed statement does not establish the pressure rating a commercial door needs. Wind speed is one input. The product evidence and project comparison are expressed in positive and negative pressure, usually in psf, under a stated basis.

A manufacturer may use wind-speed language in marketing or a preliminary selection tool. That language is not a substitute for the project-required +DP and −DP, the exact product rating, or the installation evidence. DASMA’s PSF-versus-MPH guidance makes the same distinction. (DASMA TDS 194)

Terms people swap for each other

Scroll horizontally to view all columns.

Wind-load terms and common confusions
TermWhat it means hereWhat it does not mean
Basic design wind speedA site hazard input under a named ASCE 7 edition and risk categoryThe final door pressure or product rating
Project-required design pressureThe positive and negative pressure the opening must resistA generic value for the whole city or state
Door design-pressure ratingThe manufacturer-stated +DP and −DP for the exact documented assemblyProof that the project installation and wall match
Test pressurePressure imposed during a stated laboratory procedureA higher usable design rating
Allowable stress design (ASD)A load basis used for allowable-stress comparison and many product ratingsThe same thing as ultimate/strength basis
Ultimate or strength basisA different load basis used in structural design and wind-speed mapsA number to compare directly with an ASD label without reconciliation
Effective wind areaThe area used to determine external pressure coefficients; for a typical single-unit door, the overall door areaAutomatically one panel—or automatically width × height for every complex assembly
Impact resistantSupported by the applicable impact and, where required, cyclic-pressure evidenceMerely having a high static psf rating
Operational wind loadDoor operation while wind is acting on it, under a stated manufacturer or project methodThe closed-door static design-pressure rating

Sources: DASMA TDS 168, TDS 178, TDS 194, and the DASMA standards index.

The 0.6 factor—and the trap in it

ASCE 7 wind criteria and product ratings can appear on different load bases. DASMA’s guides state that their published values already include the 0.6 allowable-stress factor. The 2024 IBC model-code provisions also use a 0.6 conversion in stated contexts.

That does not mean every pressure number should be multiplied by 0.6. First establish:

  1. What the supplied number represents.
  2. Which ASCE 7 and code edition applies.
  3. Whether the governing method permits the conversion.
  4. Whether the number was already converted.
  5. Whether the product rating is on the same basis.

Illustrative arithmetic only: if a project document expressly identifies a required strength-basis pressure of +30/−34 psf and the governing method permits conversion, 0.6 × 30 = +18 psf and 0.6 × 34 = −20.4 psf on the allowable-stress basis. If the project document already supplies ASD pressure, applying 0.6 again would be wrong.

Sources: DASMA TDS 155y, note 1; DASMA TDS 168, load-basis discussion; 2024 IBC Chapter 17.

Test pressure is not a second rating

The 2024 IBC model provision says each covered assembly is tested for 10 seconds at a load equal to 1.5 times design pressure. That is a test requirement, not permission to relabel the door at the higher value.

For an ASD design pressure of 25 psf, the stated model-code test load is:

25 psf × 1.5 = 37.5 psf

The assembly is still documented by its design-pressure rating, test standard, model/configuration, and drawing. (2024 IBC §1709.5.2)

Effective wind area changed in the 2016 ASCE cycle

DASMA explains that older wording could be read as using each structural component of a garage door as the effective wind area. The ASCE 7-16 wording treats a typical single-unit door assembly as one unit, so its overall area is used. (DASMA TDS 178)

That does not create a do-it-yourself pressure calculation. It does mean an older specification based on one section’s area may deserve review by the project design professional. Complex, mulled, or unusual assemblies still need the applicable manufacturer and engineering treatment.


How much can exposure category move the number?

Exposure category is one of the largest variables in the DASMA guide scenarios. It describes the terrain and obstructions around the project, and it belongs to the project design process—not to a door supplier’s guess.

DASMA publishes these ASCE 7-22 multipliers relative to its Exposure B chart values:

Scroll horizontally to view all columns.

DASMA Exposure C and D multipliers by roof height
ExposureMean roof heightMultiplier versus Exposure BIncrease over B
C15 ft1.4949%
C25 ft1.4444%
D15 ft1.8181%
D25 ft1.7373%

Source: DASMA TDS 155y, Exposure C and D chart notes. These multipliers apply to the guide’s stated equations, heights, and assumptions; they are not universal project factors.

What that looks like in one published guide scenario

For a 14 ft × 14 ft commercial door, 25 ft mean roof height, and 140 mph basic wind speed, TDS 155y publishes an Exposure B value of +14.7/−16.4 psf.

● Uptime calculation using DASMA’s published value and multiplier:

Scroll horizontally to view all columns.

Worked exposure multiplier values
ExposurePositiveNegativeCalculation
B+14.7 psf−16.4 psfPublished guide value
C+21.2 psf−23.6 psf14.7 × 1.44; 16.4 × 1.44
D+25.4 psf−28.4 psf14.7 × 1.73; 16.4 × 1.73

Source inputs: DASMA TDS 155y, commercial-door charts and Exposure C/D notes. Rounded to one decimal place. This is a guide example, not a project design pressure.

The arithmetic shows why exposure deserves attention. It does not prove that the example building is Exposure B, C, or D, and it does not show that a particular project fits the guide limits.

How the three categories are described

DASMA’s TDS 193 summarizes the ASCE exposure categories:

  • Exposure B covers urban, suburban, wooded, or similarly obstructed terrain where the qualifying roughness extends far enough upwind under the standard’s rules.
  • Exposure C covers open terrain with scattered obstructions generally less than 30 ft high, including open country and grasslands.
  • Exposure D covers the most severe open-water and unobstructed shoreline conditions within the standard’s stated distance and direction rules.

The exact determination is not a neighborhood label. It depends on the project location, upwind direction, distance, building height, and governing ASCE edition. (DASMA TDS 193)

The assumption worth checking

TDS 193 says ASCE 7 commentary indicates that roughly 60% to 80% of buildings may correspond to Exposure B and warns that the IBC can lead to a tendency to assume Exposure C in cases where B may apply. That is an attributed commentary statement, not a Uptime estimate and not a reason to change a project classification without the responsible design or AHJ decision. (DASMA TDS 193)

A fair question is:

Which exposure category did the project use, and where is that decision recorded?

Exposure can also change as surrounding buildings or terrain conditions change, so an old calculation is not automatically transferable to a new project.


What changed in DASMA’s ASCE 7-22 guide?

Within the matched scenarios DASMA publishes in both its ASCE 7-16 and ASCE 7-22 guides, the pressure values changed little. That result is specific to the paired guide cells. It does not prove that the site wind speed, adopted code, risk category, tornado check, or final pressure at a real address stayed the same.

How we compared the guides

DASMA TDS 155v charts selected scenarios under ASCE 7-16. DASMA TDS 155y charts corresponding scenarios under ASCE 7-22 and the 2024 IBC.

We joined every row that shared the same:

  • Door group.
  • Exposure category.
  • Mean roof height.
  • Door size.
  • Basic wind speed.
  • Pressure direction.

We then calculated:

magnitude_change_psf = |ASCE 7-22 source value| − |ASCE 7-16 source value|

percent_change =
(|ASCE 7-22 source value| − |ASCE 7-16 source value|)
÷ |ASCE 7-16 source value| × 100

Rows at 9.6 psf in both guides were flagged because a shared chart floor can hide what an unconstrained equation would have done. The public CSV contains each matched scenario, the derived change, the direction, the floor flag, and both source-page locators. It does not republish both source tables wholesale.

What the comparison shows

● Calculated from DASMA TDS 155v and TDS 155y:

Scroll horizontally to view all columns.

ASCE 7-16 versus ASCE 7-22 matched-row comparison
ScopeNon-floor rows comparedWent downUnchangedWent upMean percentage changeLargest absolute percentage change
All comparable rows38319812065−0.39%1.90%
Exposure B215179360−0.84%1.90%
Exposure C8466414+0.08%0.95%
Exposure D84132051+0.27%0.78%
15 ft mean roof height184667939−0.06%0.95%
25 ft mean roof height1991324126−0.71%1.90%
Garage-door sizes13989455−0.58%1.90%
Commercial-door sizes2441097560−0.29%0.95%

Source and method: Uptime calculation from DASMA TDS 155v and TDS 155y. There are 428 matched scenario-direction rows in total. Forty-five equal 9.6 psf in both guides and are excluded from the percentage summary. Maximum absolute magnitude change across all 428 rows: 0.5 psf. Values verified 19 September 2026. Download the 428-row derived comparison.

Three things stand out.

Exposure B never rose in the non-floor matched rows. It fell in 179 and was unchanged in 36.

Exposure D more often rose than fell. It rose in 51 of 84 non-floor rows, fell in 13, and was unchanged in 20.

Edition-to-edition cell changes were small beside the guide’s exposure multipliers. That comparison is descriptive, not a universal measure of which design variable matters most. A real project can still change materially because the applicable map, risk category, site conditions, adopted edition, or other inputs changed.

The ASCE 7-22 tornado note

TDS 155y includes a note for Risk Category III and IV buildings directing the user to ASCE 7-22 Chapter 32 to determine whether tornado pressure exceeds the wind pressure. That note is absent from TDS 155v. (DASMA TDS 155y, general note 4)

That is not a statement that every hospital, fire station, assembly building, or essential facility has a higher door pressure. It is a required comparison under the applicable ASCE 7-22 path.

What this comparison does not tell you

It does not show:

  • Whether the mapped wind speed at a project address changed.
  • Whether the jurisdiction adopted either edition.
  • Whether local amendments apply.
  • Whether the project fits the DASMA chart assumptions.
  • Whether the building is Risk Category III or IV.
  • Whether tornado pressure governs.
  • Whether the door assembly, support, or installation is acceptable.

Use the comparison to understand the published guide delta—not to bypass the project design criteria.


What does the model code say about testing and labels?

The 2024 IBC model-code text gives a clear baseline for exterior door testing and for garage and rolling door labels. The locally adopted edition still controls.

The 2024 IBC baseline in plain English

Scroll horizontally to view all columns.

2024 IBC wind-door testing and labeling provisions
Model-code provisionPlain-English result
§1709.5.2Design pressure for testing is calculated under Chapter 16; each covered assembly is tested for 10 seconds at 1.5 times design pressure
§1709.5.2.1Garage and rolling doors may be tested under ASTM E330 or ANSI/DASMA 108 and must meet ANSI/DASMA 108 pass/fail criteria
§1709.5.2.1The permanent label identifies manufacturer, model/series, positive and negative design pressure, installation-drawing reference, and test standard
§1709.5.3The cited model-code section addresses protection of exterior glazed openings in wind-borne-debris regions

Source: 2024 IBC Chapter 17, §§1709.5.2–1709.5.3. This table paraphrases the official text rather than reproducing the section wholesale.

ANSI/DASMA 108-2017 is titled Standard Method for Testing Sectional Garage Doors and Rolling Doors: Determination of Structural Performance Under Uniform Static Air Pressure Difference. DASMA’s current standards index still lists that edition. (DASMA standards)

Why the exact test and report still matter

A code section naming a test method does not establish that a particular door passed it at the required pressure, size, and configuration. The submittal still needs the exact product evidence:

  • Manufacturer and model or series.
  • Door size and configuration.
  • Positive and negative design-pressure rating.
  • Test or evaluation report.
  • Installation drawing and revision.
  • Reinforcement, track or guide, bracket, anchor, and substrate details.
  • Glazing and impact evidence where applicable.
  • Any product-approval or regional-program record.

The 2024 IBC also says test specimens and construction must be representative of the materials, workmanship, and details normally used in practice. (2024 IBC §1709.7)

Why a guide table and a project pressure schedule can differ

DASMA’s FAQ explains that a wide door can overlap more than one wall-pressure zone, so a weighted-average treatment may be used under the stated method. The project pressure schedule may use a more specific calculation, geometry, or zone assignment. (DASMA TDS 168)

Neither source should be stripped of its assumptions. The project’s accepted pressure schedule is what the product submittal needs to meet.

Which current DASMA guide is closest to the project path?

Scroll horizontally to view all columns.

DASMA guide basis and intended use
GuidePublished basisUse on this page
TDS 155vASCE 7-16; 2018 and 2021 IBC pathSource for the older side of the paired comparison
TDS 155yASCE 7-22; 2024 IBC pathSource for the newer side, exposure multipliers, and tornado note
DASMA TDS indexAdditional national, state, residential, Canadian, rolling-door, and high-performance-door guidanceFind the document that matches the actual code and equipment path

Source: DASMA’s official Technical Data Sheets index and the guide covers. A guide is not an adopted code or project approval.

The guide boundary conditions

TDS 155v and TDS 155y state important assumptions and limits. The published values are not a universal lookup for every opening.

Among the stated conditions:

  • Enclosed-building assumptions.
  • Topographic factor of 1.00.
  • Ground-elevation factor of 1.00.
  • Mean roof height no greater than 25 ft.
  • Door area and wall-zone-overlap limits printed in the guide.
  • Chart-specific roof-slope conditions.
  • Separate garage-door and commercial-door chart notes.

The commercial-door tables in TDS 155y are limited to roof slopes of 10 degrees or less. The garage-door tables use their own roof-slope treatment and notes. The guide sends openings outside its limits back to an ASCE 7 determination. (DASMA TDS 155y)


Are pressure rating and impact rating the same?

No. Static design-pressure resistance and debris-impact resistance answer different questions and use different evidence.

A door can have a high positive and negative pressure rating without having the required impact qualification. An impact-qualified assembly still needs to meet the project’s static pressure requirement.

What each evidence type proves

Scroll horizontally to view all columns.

Wind-load evidence types and their limits
EvidenceMain question it answersWhat it does not prove by itself
Static pressure test or evaluationCan the exact assembly resist the stated positive and negative pressure under the test method?Debris impact, correct project installation, or supporting-wall adequacy
Missile-impact evidenceDid the exact assembly meet the stated impact procedure?Static pressure adequacy at the project requirement
Cyclic-pressure evidenceDid the assembly survive the stated pressure cycles after impact or under the program method?A different jurisdiction’s acceptance
Product approval or NOADoes the named program recognize the exact product within listed limits?Universal acceptance outside that program or compliance with a different installation

Sources: 2024 IBC §1709.5.3, DASMA standards, and the official Florida and Texas program sources in the next section.

Which impact standard applies?

DASMA currently lists ANSI/DASMA 115-2017, titled Standard Method for Testing Sectional Garage Doors: Determination of Structural Performance Under Missile Impact and Cyclic Wind Pressure. The 2024 IBC §1709.5.3 text cited on this page addresses exterior glazed openings and names ASTM E1886 and ASTM E1996 for impact protective systems. Florida, Miami-Dade, Texas, a project specification, or an insurer may use additional or different accepted paths.

Do not choose an impact standard from a generic article. The project needs the exact adopted code, opening type, program, test edition, report, and product configuration.

What glazing changes

Adding glazing does not by itself rewrite the building’s required design pressure for the opening. It can change the product configuration, impact requirement, approval record, and maximum qualified size. The submittal should identify the glazing type, location, and extent and match the exact report or drawing. (DASMA TDS 168; DASMA TDS 181)

A fire rating is another separate program. If the opening also uses a rolling fire door, see fire door drop test requirements.


What proof do Florida, Miami-Dade, and Texas use?

The model-code baseline is only the first layer. Florida’s state product database, Miami-Dade’s Product Control program, and the Texas windstorm program add their own records and project steps.

This section is not a 50-state survey. It shows three current, verifiable examples of why “tested door” and “accepted project” are not the same statement.

The model-code baseline

Under the 2024 IBC example, start with:

  1. Project-required positive and negative pressure.
  2. Exact manufacturer and model or series.
  3. Exact size and configuration.
  4. Applicable test or evaluation evidence.
  5. Permanent label fields.
  6. Referenced installation drawing.
  7. Attachment and supporting-structure evidence.
  8. Inspection and AHJ acceptance.

Florida statewide

The Florida Building Commission identifies the Florida Building Code, 8th Edition (2023) as effective December 31, 2023. Its Product Approval search identifies the current code version and lets a user filter or review fields including:

  • Approved for use in the High-Velocity Hurricane Zone.
  • Approved for use outside the HVHZ.
  • Impact resistant.
  • Positive design pressure.
  • Negative design pressure.
  • Product model, number, or name.
  • Evaluation and installation documents in the exact product record.

Sources: Florida Building Commission and Florida Product Approval Search, verified 19 September 2026.

The database record is not a substitute for reading the exact documents. Match:

  • FL number and revision.
  • Manufacturer and model.
  • Opening size.
  • Door construction and options.
  • Impact status.
  • HVHZ or outside-HVHZ status.
  • Positive and negative pressure.
  • Installation instructions.
  • Limits of use.
  • Current code version and approval status.

Florida’s site also shows materials related to a 2026 code update process. This page does not assign a future effective date that the Commission has not verified on the current official page.

Miami-Dade Product Control

Miami-Dade maintains a separate Product Control and Notice of Acceptance (NOA) search. Current search results list exact product descriptions and expiration dates. For example, the official database contains current commercial sectional and rolling-door NOAs with named maximum widths, glazing options, and expiration dates. Those are product-specific examples, not general ratings. (Miami-Dade Product Approval; current Product Control example)

For an HVHZ project, verify:

  • Exact current NOA number.
  • Applicant/manufacturer.
  • Door series and size.
  • Impact status and glazing configuration.
  • Positive and negative pressure.
  • Approved drawings and installation details.
  • Substrate and anchor limits.
  • Expiration date.
  • Any project-specific product-control or building-department requirement.

Miami-Dade still posts older application checklists in its forms library. A dated checklist can help explain the evidence program, but it should not replace the current exact NOA, current code, or project instructions.

Texas TDI/TWIA windstorm program

Texas states that Applications for Certificate of Compliance (WPI-1) starting April 1, 2026 must be certified under the 2024 IRC or 2024 IBC. Construction must be certified to be eligible for windstorm coverage through the Texas Windstorm Insurance Association. TDI also says:

  • The designated catastrophe areas did not change with the code adoption.
  • Required wind speed is determined for each structure based on location.
  • The ASCE Hazard Tool is one official resource named for the lookup.
  • Most designated catastrophe areas are now in the wind-borne-debris region.
  • Debris requirements follow the 2024 codes for the program.

Source: Texas Department of Insurance, Adopted Building Codes, verified 19 September 2026.

TDI’s product-evaluation FAQ was last updated in July 2025, before the April 2026 code transition, and still cites older editions in places. It remains useful for understanding label and evaluation evidence, but where it conflicts with the current adopted-code page, use the current program requirements and obtain project guidance. (TDI Product Evaluations FAQ)

TDI also warns that posting a link to a third-party evaluation report does not itself mean the report proves compliance. (TDI Product Evaluations)

The proof layers side by side

Scroll horizontally to view all columns.

Wind-load proof layers: product evidence and project acceptance
PathCurrent top-level item to verifyProduct evidence to matchProject acceptance still needed?
IBC model-code baselineLocally adopted edition and amendmentsLabel, report, exact drawing, exact configurationYes
Florida statewide8th Edition (2023) and exact Florida Product Approval recordFL record, limits, impact/HVHZ fields, ±DP, instructionsYes
Miami-Dade Product ControlExact current NOA and expirationNamed series, size, options, ±DP, impact status, drawingsYes
Texas TDI/TWIACurrent WPI-1 code path, location, and certification processAccepted product evidence plus exact project installationYes

Sources: official ICC, Florida Building Commission, Miami-Dade Product Control, and Texas Department of Insurance pages linked above. “Yes” means the product record is one part of the project evidence, not automatic approval of the installed opening.


How do I check the door in front of me?

Start with the project pressure schedule, then read the permanent label, obtain the exact drawing it references, and compare the installed assembly and load path with the accepted evidence. A label without the project requirement or drawing is incomplete proof.

DASMA’s inspection guidance is direct: do not rely on a wind-load label alone. Garage doors are assembled on site from components that can be configured in different ways and quantities. (DASMA TDS 181)

What the 2024 IBC model-code label identifies

Scroll horizontally to view all columns.

2024 IBC permanent-label fields
FieldWhy it mattersWhat to compare it with
ManufacturerIdentifies the source of the assembly evidenceReport, order, drawing, product record
Model or seriesConnects the installed door with the tested/evaluated familyExact submittal and label
Positive design-pressure ratingSupplies one direction of the assembly ratingProject-required positive pressure on the same basis
Negative design-pressure ratingSupplies the suction/outward-direction ratingProject-required negative-pressure magnitude on the same basis
Installation-drawing referenceConnects the label to the configuration and attachment detailsExact drawing number and revision
Applicable test standardIdentifies the stated evaluation pathCode, report, and program requirement

Source: 2024 IBC §1709.5.2.1. The positive and negative pressure values are two fields within the provision’s five named label categories.

Additional program records

Scroll horizontally to view all columns.

Additional Florida, Miami-Dade and Texas program records
ProgramWhere to verify the extra evidence
Florida Product ApprovalExact FL record, code version, HVHZ/outside-HVHZ, impact field, ±DP, reports, instructions, limits of use
Miami-Dade Product ControlExact current NOA, product description, drawings, ratings, options, and expiration
TDI/TWIACurrent certification path, project location, accepted report or evaluation, label evidence, and inspection/certificate records

Sources: Florida Product Approval Search, Miami-Dade Product Approval, and TDI Adopted Building Codes.

The 20-step verification checklist

This checklist is Uptime’s source-grounded assembly of the code, guide, product-record, and field-evidence steps. It does not calculate the project pressure or approve the installation. Download the source-linked CSV.

Before you buy

Scroll horizontally to view all columns.

Wind-rated door verification checklist: before you buy
#CheckWhy it matters
1Obtain the required positive and negative design pressures in psf, with the pressure basis identifiedA wind speed or one unsigned number does not establish the door requirement
2Confirm the adopted code, ASCE 7 edition, and local amendmentsThe newest model code does not automatically govern
3Confirm the exposure category and who determined itExposure can materially change the published guide pressure
4Confirm opening dimensions, wall location, mean roof height, enclosure, and effective-wind-area treatmentThese affect pressure and whether a guide applies
5Ask whether impact resistance is required for this exact openingStatic pressure and impact/cyclic evidence are separate
6For Florida work, open the exact current Product Approval recordHVHZ, outside-HVHZ, impact, and ±DP are separate fields
7For Miami-Dade Product Control work, open the exact current NOA and expirationA similar or expired NOA is not a match
8For TDI/TWIA work, confirm the current 2024-code certification path and official project locationThe program is location- and application-specific

Sources: ICC, ASCE, DASMA, Florida Building Commission, Miami-Dade, and TDI source rows 1–8 in the downloadable checklist.

On the quote

Scroll horizontally to view all columns.

Wind-rated door verification checklist: on the quote
#CheckWhy it matters
9Confirm the rating covers the exact model, width, height, configuration, reinforcement, glazing, and operationA model-family page does not establish one rating for every assembly
10Request the exact wind-load installation drawing and revisionThe drawing carries the rated configuration and attachment details
11Identify who will verify jambs, header, wall, and supporting structure for the manufacturer’s reactionsThe door rating does not prove the building-side support

Sources: DASMA TDS 180, TDS 181, and 2024 IBC §1709.5.2.1.

At delivery and installation

Scroll horizontally to view all columns.

Wind-rated door verification checklist: delivery and installation
#CheckWhy it matters
12Read and photograph the permanent label from a safe positionIt connects the installed door to the model, rating, drawing, and test evidence
13Reject a submittal that supplies only an mph claim without comparable project ±PSFMph alone does not establish the pressure match
14Compare reinforcement location, size, quantity, and fasteners with the drawingThe rating depends on the documented configuration
15Compare stiles, hinges, rollers, retainers, tracks or guides, brackets, and spacingThese components transfer pressure through the assembly
16Compare jamb-to-structure anchors, substrate, quantity, spacing, embedment, and edge distanceThis is the load path into the building
17Confirm required locks, wind posts, windlocks, or other setup-dependent parts are presentSome ratings depend on those components
18If glazed, confirm glazing type, location, and extent match the evidenceGlazing can change the approved configuration and impact evidence

Source: DASMA TDS 181, with project and product-program checks mapped in the downloadable CSV.

At closeout and after a high-wind event

Scroll horizontally to view all columns.

Wind-rated door verification checklist: closeout and post-event
#CheckWhy it matters
19Retain the pressure schedule, label photo, exact drawing, reports, approvals, approved requests for information (RFIs), inspection records, and AHJ/program acceptanceFuture replacement, insurance, audit, and repair decisions depend on the evidence chain
20After a severe event or visible damage, observe only from a safe position; keep clear of springs, cables, brackets, and stored-energy parts; stop using a damaged, binding, or unsafe door and obtain a trained evaluationOccupant observation and technician-level operation or repair are different tasks

Sources: DASMA TDS 174 and TDS 175 through the official TDS index, TDS 175, and the stored-energy warning in TDS 181. This does not mean every undamaged door requires a technician before any post-storm operation.

The arithmetic for a documented pressure comparison

Only compare values after confirming that they use the same basis and apply to the exact assembly.

Illustrative example:

  • Project document expressly gives +30/−34 psf on a strength basis.
  • The governing method permits the 0.6 conversion.
  • The exact door label gives +20/−22 psf on the ASD basis.
Required positive ASD = 30 × 0.6 = 18.0 psf
Required negative ASD magnitude = 34 × 0.6 = 20.4 psf

Positive margin = 20 − 18.0 = 2.0 psf
Negative margin = 22 − 20.4 = 1.6 psf

That is a basic numerical pressure match in both directions. It does not verify:

  • The conversion is permitted for the real project.
  • The exact size and configuration.
  • Impact status.
  • Drawing and anchors.
  • Supporting wall and load path.
  • Product approval.
  • Installation.
  • AHJ or program acceptance.

The 2024 IBC’s stated test load for an 18.0 psf design pressure would be 27.0 psf, and for 20.4 psf it would be 30.6 psf, because design pressure × 1.5 = test pressure under the cited provision. That test arithmetic is not a second design rating. (2024 IBC §1709.5.2)


Can I verify a door that is already installed?

You can inventory the evidence and identify gaps. You cannot establish project compliance from a label or visual inspection alone.

Scroll horizontally to view all columns.

Evidence available for an installed commercial garage door
What you haveWhat you can concludeWhat to do next
Label, exact drawing, project ±DP, configuration records, and acceptance all matchA strong documentation chain existsPreserve it and confirm no later modification broke the match
A label, but no project pressureThe assembly rating is partly documented; project suitability is unknownObtain the accepted project pressure schedule
Project pressure, but no readable label or product evidenceThe requirement is known; the assembly rating is not establishedIdentify the manufacturer/model and obtain accepted evidence
Label numbers match, but the drawing is missingA numerical match onlyGet the exact referenced drawing and revision
Components were changed or removedThe old evidence may no longer describe the installed assemblyObtain accepted revised documentation before relying on the old rating
Tracks, guides, jambs, anchors, panels, or curtain are damagedThe load path or rated configuration may be compromisedStop relying on appearance and obtain a qualified evaluation
Impact is required but only static pressure evidence existsThe evidence is incompleteObtain the exact impact/cyclic qualification
A Florida, Miami-Dade, or TDI report is similar but not exactNo product/project match has been establishedFind the exact current record and limits
No traceable evidence existsCapacity is unknown—not automatically zeroDocument what exists and seek manufacturer, design-professional, and AHJ guidance

Editorial framework built from DASMA TDS 180, TDS 181, the Florida Product Approval database, Miami-Dade Product Control, and TDI program guidance.

Unknown is not zero. A missing label or report is an evidence gap. Do not invent a rating from the number of struts, the apparent panel thickness, a model-family brochure, or a similar door nearby.

A facility representative can safely:

  • Photograph a visible label without entering a hazard area.
  • Record the opening ID and dimensions.
  • Gather permits, orders, drawings, and maintenance records.
  • Record visible damage without touching springs, cables, brackets, or loose components.
  • Compare document identifiers and revisions.
  • Use the checklist to identify missing evidence.

If the problem is operational—binding, crooked travel, damaged track, a broken operator, or a door that will not close—that is a different search job. See commercial overhead door problems.


Does a wind-rated door still open in wind?

Not necessarily. A static wind rating describes the closed assembly under the stated pressure test. Opening and closing while wind acts on the door is a separate performance question.

DASMA reported in Summer 2025 that operational wind load was being requested more often, that manufacturers used their own methods, and that its Rolling Door Division Research Committee had begun work toward a standard test method with initial testing at Intertek in York, Pennsylvania. (Door + Access Systems, Summer 2025 Tech Corner)

As of the 19 September 2026 verification date, the DASMA standards index did not list a separately titled operational-wind test standard. That index check does not prove that no broader product standard contains a related provision.

If a specification calls for operational wind performance, require the manufacturer to state:

  • The test or calculation method.
  • Door model, size, and configuration.
  • Wind-pressure direction and magnitude.
  • Whether the door was opening, closing, or holding position.
  • Cycle count and acceptance criteria.
  • Required controls, guides, windlocks, or operating restrictions.
  • Whether the result is independently tested, manufacturer-tested, or calculated.

A correctly rated closed door may still be unsafe or unable to move under wind. Windlocks, guide contact, curtain pressure, panel deflection, seals, and the operator all affect operation. Do not improvise operation during a storm or bypass an interlock to make a door move.


Which mistakes break a wind-load submittal?

Scroll horizontally to view all columns.

Wind-load submittal mistakes and corrections
MistakeCorrection
Buying by mph aloneObtain the project-required positive and negative pressure in psf on a stated basis
Treating 9.6 psf as a universal national minimumTreat it as the minimum charted inside the stated DASMA guide assumptions
Checking only one pressure directionCompare both positive and negative ratings
Mixing ASD, ultimate, and test pressureIdentify each value before doing arithmetic; never apply 0.6 automatically or twice
Treating impact-rated and pressure-rated as synonymsRequire separate evidence for each applicable performance question
Relying on a model-family pageMatch exact model, size, options, reinforcement, glazing, and revision
Assuming the label is the whole proofObtain the exact drawing, report, installation record, and project pressure
Assuming the door rating covers the wallVerify reactions, jambs, anchors, substrate, framing, and continuous load path
Using a similar Florida, Miami-Dade, or Texas recordFind the exact current record and limits of use
Removing struts, posts, windlocks, locks, or other parts for clearancePreserve the documented configuration unless accepted revised evidence authorizes a change
Treating a missing label as zero capacityRecord it as an evidence gap and resolve it
Treating static rating as proof of operation in windAsk for the manufacturer’s stated operational method and limits

Sources: summary of the cited ICC, ASCE, DASMA, Florida Building Commission, Miami-Dade Product Control, and TDI evidence above; see the source register and downloadable crosswalk for row-level provenance.


Methodology

What we did. We opened the primary sources named on this page at the issuer’s site or official publishing platform and rechecked them on 19 September 2026. For PDFs, we read the relevant pages and chart notes. We recorded the publisher, document title, edition or revision where stated, exact locator, verification date, authority type, and scope limitation.

How we built the cross-edition comparison. We transcribed the matched scenario values from DASMA TDS 155v and TDS 155y, joined the rows by door group, exposure, mean roof height, door size, basic wind speed, and pressure direction, and calculated the change in pressure magnitude. The public 428-row CSV publishes the scenario, derived change, direction, floor flag, and source-page locators. It does not republish both DASMA pressure tables wholesale.

The formulas. For each matched row:

magnitude_change_psf = |7-22 source value| − |7-16 source value|

percent_change =
(|7-22 source value| − |7-16 source value|)
÷ |7-16 source value| × 100

For the exposure worked example:

Exposure C or D example value =
DASMA’s published Exposure B value × DASMA’s published multiplier

All arithmetic was recalculated with a tool. The CSV, JSON, article summary, and worked example were then checked against one another.

What ★ and ● mean.

  • ★ Source-reported: checked in the named primary source.
  • ● Calculated: computed from verified source inputs with the formula shown.

Neither symbol means “less verified.” A calculated value is publishable only when its inputs, formula, unit, and scope are all clear.

Source hierarchy. We used:

  1. Official adopted-program and governmental material.
  2. Official model-code text and publisher adoption statements.
  3. Official standard-publisher pages.
  4. DASMA technical data sheets and standards indexes.
  5. Manufacturer material only where an exact named product example would be useful.
  6. Uptime’s transparent calculations and editorial organization.

What we did not do. We did not:

  • Calculate a project design pressure.
  • Inspect, test, install, repair, certify, or approve a door.
  • Read the complete paid text of ASCE 7, ASTM E330, ANSI/DASMA 108, or ANSI/DASMA 115 clause by clause.
  • Reproduce protected standards tables or both DASMA chart sets wholesale.
  • Survey every state or local code adoption.
  • Complete a repository-level or XML-sitemap inventory of every Uptime route from this research environment.
  • Claim that a manufacturer specification is independent testing.
  • Assign a public reuse license to the dataset.

Missing-value rule. Unknown, unavailable, not applicable, and unverified are different states. We do not turn a missing value into zero. A missing label or report is an evidence gap, not proof of zero capacity.

Corrections. Report a moved source, calculation issue, or factual correction through the contact page. A substantive evidence change increments the dataset version and changes the visible verification date only after the sources are actually rechecked.


Limitations

  • This page cannot tell you the required pressure for a building. It explains the evidence chain and comparison method. The project design and approval process supplies the actual requirement.
  • The locally adopted code controls. The 2024 IBC is used as a current model-code example, not as a claim that every jurisdiction has adopted it.
  • The DASMA charts have stated limits. Building enclosure, topography, elevation, mean roof height, roof slope, opening area, wall zone, and other conditions can put a project outside them.
  • The 9.6 psf value is a chart floor in TDS 155y, not a universal project minimum.
  • The 428-row comparison holds wind speed and the other matched scenario labels constant. It does not capture a changed wind map or site-specific project calculation.
  • The exposure multipliers are those printed in TDS 155y for its guide method. They are not a universal multiplier for every building.
  • The jurisdiction section covers the model-code baseline plus Florida, Miami-Dade, and the Texas windstorm program. It is not a 50-state or every-county survey.
  • The Texas product-evaluation FAQ predates the April 2026 code transition. The current adopted-code page and project instructions control where the pages differ.
  • Miami-Dade’s older forms and checklists remain useful background but do not replace the current exact NOA or current project requirements.
  • Manufacturer and product-program evidence is configuration-specific. A named series or family page does not establish a rating for every size or option.
  • No separately titled operational-wind test standard was identified on DASMA’s current standards index. That index check does not establish the contents of every broader product standard. Manufacturer claims may use different methods.
  • Source URLs, product approvals, editions, and TDS revisions change. Verify the current record before a submittal.

Sources

Every source below was checked at the issuer’s site or official publishing platform on 19 September 2026. The downloadable source register adds exact locators, authority type, scope used, and limitations.

Model code and structural-load sources

Scroll horizontally to view all columns.

Model-code and structural-load sources
IssuerDocumentEdition or statusUsed for
International Code CouncilInternational Building Code overviewCurrent overviewModel-code adoption and local-amendment status
International Code Council2024 IBC Chapter 172024 IBCTest pressure, garage/rolling-door test methods, label fields, impact scope
American Society of Civil EngineersASCE/SEI 7-22ASCE 7-22Current standard-publisher overview
American Society of Civil EngineersAbout the ASCE Hazard ToolSupports ASCE 7-10, 7-16, and 7-22Site lookup, edition selection, wind and debris-region data

DASMA standards and technical guidance

Scroll horizontally to view all columns.

DASMA standards and technical guidance
IssuerDocumentEdition or revisionUsed for
DASMAStandards indexCurrent indexANSI/DASMA 108-2017, 115-2017, and current standards inventory
DASMATechnical Data Sheets indexCurrent indexCurrent document inventory and TDS scope warning
DASMATDS 155vRev. 4/26ASCE 7-16 guide values in the paired comparison
DASMATDS 155yRev. 1/26ASCE 7-22 guide values, multipliers, limits, and tornado note
DASMATDS 168Rev. 3/26Roles, pressure terms, orientation, glazing, impact, support, and weighted-average guidance
DASMATDS 178Rev. 10/22Effective wind area
DASMATDS 180Reaffirmed 06/20Size-dependent ratings and evidence for untested sizes
DASMATDS 181Rev. 6/25Label-alone warning, 15-item configuration inspection, safety boundary
DASMATDS 193Rev. 1/22Exposure categories and responsibility
DASMATDS 194Current PDFPSF versus mph distinction
DASMATDS 1502Rev. 6/24Job-specific ratings and label context
DASMA / Door + Access SystemsTech Corner: operational wind loadSummer 2025Static-versus-operational distinction and test-method development

Florida, Miami-Dade, and Texas program sources

Scroll horizontally to view all columns.

Florida, Miami-Dade and Texas program sources
IssuerDocumentCurrent date or statusUsed for
Florida Building CommissionCommission home page8th Edition (2023), effective December 31, 2023Current Florida code edition
Florida Building CommissionProduct Approval Search2023 FBC databaseHVHZ, outside-HVHZ, impact, ±DP, and exact product records
Miami-Dade County Product ControlProduct ApprovalCurrent program pageNOA workflow
Miami-Dade County Product ControlCurrent garage-door NOA example listAccessed September 2026Product-specific descriptions and expiration dates
Texas Department of InsuranceAdopted Building Codes2024 IBC/IRC path for applications starting April 1, 2026Current windstorm-program edition, location, and debris guidance
Texas Department of InsuranceWindstorm General InformationUpdated April 2, 2026Code effective-date table
Texas Department of InsuranceProduct Evaluations FAQUpdated July 21, 2025Product/label guidance with pre-transition caveat
Texas Department of InsuranceProduct EvaluationsUpdated June 13, 2025Third-party report disclaimer

How to cite this page

Dataset name: Uptime Commercial Door Wind Load Evidence Ledger
Version: 1.1.0
Publisher: Uptime Dock & Door Research
Compiled and last verified: 19 September 2026

Suggested citation:

Uptime Dock & Door Research. “Commercial Garage Door Wind Load Requirements: What the Code Asks For and What Proves It.” Uptime Dock & Door. Uptime Commercial Door Wind Load Evidence Ledger, version 1.1.0. Last verified September 19, 2026. https://uptimedockanddoor.com/research/commercial-garage-door-wind-load-requirements/

When citing the cross-edition finding, carry these qualifications with it:

  • It compares 428 matched scenario-direction rows in DASMA TDS 155v and TDS 155y.
  • The source pressure values belong to DASMA.
  • Uptime calculated the row-level magnitude and percentage changes.
  • Forty-five rows are at the shared 9.6 psf chart floor.
  • The comparison does not capture a changed site wind map or project calculation.

No public reuse license is asserted for the dataset. Third-party source material remains subject to its original rights.


Download the data

Seven CSVs and one combined JSON. The six evidence tables contain 568 rows; the separate data dictionary contains 59 field-definition rows. No sign-up or email gate.

Scroll horizontally to view all columns.

Commercial garage door wind-load data downloads
FileRowsWhat it contains
uptime-asce-7-16-vs-7-22-door-pressure-delta.csv428Matched scenario labels, derived pressure-magnitude change, percentage change, direction, 9.6-floor flag, and source-page locators; no wholesale copy of both source tables
uptime-wind-load-jurisdiction-crosswalk.csv39Model-code, DASMA-guide, Florida, Miami-Dade, and Texas authority statements with scope limits
uptime-vehicle-access-door-wind-document-register.csv42Official document titles, issuers, editions or revisions, questions answered, URLs, and scope notes
uptime-wind-rated-door-verification-checklist.csv20The source-linked buying, quote, installation, closeout, and post-event checklist
uptime-wind-load-terminology-crosswalk.csv13Terms, definitions, common confusions, sources, and limitations
uptime-wind-load-source-register.csv26Publisher, document, authority type, URL, edition, exact locator, use, verification date, and limitation
uptime-commercial-door-wind-load-data-dictionary.csv59Field definitions and missing-value rules for the public files
uptime-commercial-door-wind-load-evidence-ledger-v1.1.0.json568 evidence rowsAll six evidence tables, row counts, formulas, methodology, missing-value rule, limitations, and source register

Reading the files honestly:

  • Blank, unknown, unavailable, not applicable, and unverified are not zero.
  • Source-page locators show where to check the DASMA comparison rows.
  • The delta CSV contains Uptime’s derived changes, not both DASMA tables.
  • The JSON has "license": null deliberately.
  • Dataset version and source verification date change only after a substantive recheck.

Questions people ask

What psf does my commercial garage door need?

No national web page can supply one number for every building. Obtain the project-required positive and negative pressure, the pressure basis, and the adopted code edition from the accepted project design or building official.

Is 150 mph equal to one commercial-door psf rating?

No. Wind speed is one input. Exposure, height, geometry, enclosure, wall location, opening size, effective wind area, pressure basis, and other factors affect the result.

Does the direction my door faces change the requirement?

DASMA’s FAQ says worst-case wind toward and away from the door is considered, so compass direction alone is not the deciding variable. The opening’s wall zone, corner relationship, and project calculation still matter. (DASMA TDS 168)

My door size is not on the DASMA chart. What do I do?

Do not invent an interpolation rule. Obtain a project-specific pressure and exact manufacturer evidence for the proposed size. DASMA TDS 180 explains that ratings may differ by size and that untested sizes need accepted analysis or additional evidence. (DASMA TDS 180)

Is a taller building’s door requirement always higher?

Height is one pressure input, and the DASMA guides publish separate 15 ft and 25 ft mean-roof-height values. The final result still depends on the complete project method and conditions.

What is a “WindCode,” “windstorm,” or numbered manufacturer package?

It is a manufacturer’s product or option language, not a universal code classification. Ask for the exact model/configuration, positive and negative psf rating, test/evaluation evidence, and installation drawing.

Who verifies whether the wall can take the door loads?

The project needs accepted structural evidence for the supporting jambs, header, wall, anchors, and load path. DASMA separates that building-side responsibility from the door manufacturer’s rated assembly. (DASMA TDS 168; TDS 181)

Can I add struts or wind posts to make an existing door wind rated?

Field-added parts do not create a tested or approved rating by themselves. The higher rating must come from accepted manufacturer or project documentation for the exact resulting assembly.

Does a matching label mean the door is compliant?

No. It is one part of the evidence. The project pressure, pressure basis, exact size/configuration, drawing, anchors, support, impact requirement, installation, approval record, and AHJ acceptance still need to match.

Is impact resistance automatically required in every wind-borne-debris region?

Use the exact adopted code and opening type. The 2024 IBC §1709.5.3 text cited here is written for exterior glazed openings, while Florida, Miami-Dade, Texas, project specifications, or insurance programs can impose their own product and impact evidence rules.

Can a wind-rated door be operated during a storm?

A closed-door static rating does not prove operational performance. Obtain the manufacturer’s operational method, pressure, configuration, and restrictions, and do not improvise operation or bypass safety controls.