  "dataset_name": "The Commercial Door Fault Ledger",
  "version": "2.0.0",
  "compiled": "2026-09-17",
  "last_verified": "2026-09-17",
  "publisher": "Uptime Dock & Door",
  "editorial_byline": "Uptime Dock & Door Research",
  "publisher_url": "https://uptimedockanddoor.com/",
  "page_url": "https://uptimedockanddoor.com/research/commercial-overhead-door-problems/",
  "scope": "Source-based first-response reference for selected commercial sectional-door, rolling-steel-door and grille systems. Fire-door entries are limited to identification and specialist handoff. U.S.-oriented regulatory discussion; no field sample, failure frequency or universal cross-brand equivalence.",
  "license": null,
  "license_note": "No license is asserted. The compilation does not grant rights to third-party source documents, diagrams, manuals or standards. No third-party documents are distributed.",
  "row_counts": {
    "symptom-ledger": 38,
    "operator-mode-crosswalk": 7,
    "operator-fault-codes": 63,
    "constant-pressure-cause-tree": 9,
    "name-crosswalk": 41,
    "sources": 20
  },
  "technical_record_count": 158,
  "source_record_count": 20,
  "total_rows": 178,
  "derived_counts": {
    "method": "Count table records directly. Count the explicit verified individual-code list, not grouped table rows. Count YES flags in the nomenclature table, not fire-door installations.",
    "genie_balance_first_codes": [
      "39",
      "49",
      "4B",
      "51",
      "52",
      "59",
      "5C",
      "5D",
      "5E",
      "69"
    ],
    "genie_balance_first_count": 10,
    "dasma_277_starred_terms": [
      "Fusible link",
      "Dropout",
      "Flame baffle",
      "Automatic closing device, electromechanical release, or magnetic release",
      "Drop test"
    ],
    "dasma_277_starred_term_count": 5
  },
  "tables": {
    "symptom-ledger": [
      {
        "symptom_id": "S01",
        "group": "Will not close",
        "symptom_as_people_say_it": "Opens fine, but only goes down while I hold the button",
        "door_types": "Sectional; Rolling steel; Grille",
        "documented_context_not_ranked": "Configured held-button closing, or a monitored-protection restriction. Behaviour alone cannot distinguish them.",
        "safe_observation": "Use posted instructions and existing records; record only an externally visible indication.",
        "what_this_does_not_establish": "That a photo eye failed — or that anything is broken at all.",
        "stop_line": "Do not change modes or use newly required held-button closing as a workaround.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "DASMA382; LM-L5; MAN-070E; GENIE-TC; MIC-SMART",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2022/06/TDS382.pdf; https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf; https://manaras.com/book1120.pdf; https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf; https://ismartgate.com/manuals/Micanan_Pro-J_manual.pdf",
        "source_locator": "LM pp. 28–29, 36, 38; MAN p. 16; GEN codes 3A, 62, 66; MIC pp. 14, 16–19",
        "source_editions": "DASMA382: REV 05/22/22 (orig 6/26/17); LM-L5: 45-page manufacturer manual; date not stated in inspected text; MAN-070E: BOOK1120 REV 8, 2026/07/16; GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2; MIC-SMART: August 2010",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S02",
        "group": "Will not close",
        "symptom_as_people_say_it": "Starts down, then reverses all the way back up",
        "door_types": "Sectional; Rolling steel; Grille",
        "documented_context_not_ranked": "A safety input or an obstruction can cause reversal; the active input depends on the controller.",
        "safe_observation": "From outside the travel path, record visible obstructions and the message already displayed.",
        "what_this_does_not_establish": "Which device reacted, or whether a part needs replacement.",
        "stop_line": "Do not walk under the door, defeat a sensor or repeat the fault to test it.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "DASMA382; GENIE-TC; LM-L5",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2022/06/TDS382.pdf; https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf; https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "D382 pp. 1–2; GEN codes 35–38, 46, 48; LM p. 38 E4/E7",
        "source_editions": "DASMA382: REV 05/22/22 (orig 6/26/17); GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2; LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S03",
        "group": "Will not close",
        "symptom_as_people_say_it": "Will not move down at all, but opening works",
        "door_types": "Sectional; Rolling steel; Grille",
        "documented_context_not_ranked": "An active stop/protection input or a travel-limit condition can restrict closing.",
        "safe_observation": "Record the complete accessible message and whether the failure is new.",
        "what_this_does_not_establish": "Which physical device or wire is at fault.",
        "stop_line": "Trained assessment before changing limits, wiring or modes.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "LM-L5; GENIE-TC; MAN-070E",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf; https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf; https://manaras.com/book1120.pdf",
        "source_locator": "LM pp. 36–38; GEN codes 60, 66, 68, 6C; MAN Tables 1–2",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text; GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2; MAN-070E: BOOK1120 REV 8, 2026/07/16",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S04",
        "group": "Will not close",
        "symptom_as_people_say_it": "Stops a few inches off the floor, then goes back up",
        "door_types": "Sectional; Rolling steel",
        "documented_context_not_ranked": "Obstruction/safety response and travel settings need to be distinguished.",
        "safe_observation": "Note the observed stopping height; inspect the floor only from a safe position outside the opening.",
        "what_this_does_not_establish": "That a limit adjustment is the fix.",
        "stop_line": "Do not force a close or adjust travel limits.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "LM-L5; GENIE-TC; DASMA269",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf; https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf; https://www.dasma.com/wp-content/uploads/2021/03/TDS269-l.pdf",
        "source_locator": "LM p. 38 E4; GEN codes 46, 48, 5A; D269 bottom-bar/curtain checks",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text; GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2; DASMA269: Rev 2/21; issued 3/15/21",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S05",
        "group": "Will not close",
        "symptom_as_people_say_it": "Closes from the wall button but not from the remote",
        "door_types": "Sectional; Rolling steel; Grille",
        "documented_context_not_ranked": "Radio compatibility, programming and control mode are separate from the door motor.",
        "safe_observation": "Record which local control previously worked; identify the remote and operator from safe labels or records.",
        "what_this_does_not_establish": "That the receiver failed. On a named Genie platform this can be a setting.",
        "stop_line": "No board access or mode changes; use the exact remote/operator manual.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "GENIE-TC; LM-L5",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf; https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "GEN code 62; LM p. 39 radio troubleshooting R1–R5",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2; LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S06",
        "group": "Will not close",
        "symptom_as_people_say_it": "Only starts closing a few seconds after I press and hold",
        "door_types": "Sectional; Rolling steel; Grille",
        "documented_context_not_ranked": "The checked LiftMaster Logic 5.0 manual describes a delayed closing override for E7.",
        "safe_observation": "Record a delay already observed and any accessible indicator; do not hold the button to reproduce it.",
        "what_this_does_not_establish": "Which device failed, or that continued use is safe.",
        "stop_line": "Trained assessment; the override is not a repair.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "LM-L5",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "Printed p. 38 E7; p. 36 restricted-close note",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S07",
        "group": "Will not close",
        "symptom_as_people_say_it": "Works all morning, reverses on sunny afternoons",
        "door_types": "Sectional; Rolling steel",
        "documented_context_not_ranked": "The time pattern is useful evidence; the checked general sensor sheet does not identify its cause.",
        "safe_observation": "Record the time, lighting/weather and any safely visible sensor indication.",
        "what_this_does_not_establish": "That sunlight, a bracket or a failed sensor is the cause.",
        "stop_line": "Do not move, shield, bypass or replace sensors on this evidence alone.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "DASMA382",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2022/06/TDS382.pdf",
        "source_locator": "pp. 1–2 sensor installation/testing scope; time-pattern routing is editorial, not a reported cause",
        "source_editions": "DASMA382: REV 05/22/22 (orig 6/26/17)",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S08",
        "group": "Will not close",
        "symptom_as_people_say_it": "Closes, but leaves a gap at the floor on one side",
        "door_types": "Sectional; Rolling steel",
        "documented_context_not_ranked": "Visible bottom-bar/section damage, sealing and alignment need assessment.",
        "safe_observation": "Stand back and sight along the bottom edge against the floor line.",
        "what_this_does_not_establish": "That the cable drums are the cause.",
        "stop_line": "Do not adjust drums, cables or bottom brackets.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "DASMA269; CLOPAY; DASMA160",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2021/03/TDS269-l.pdf; https://www.clopaydoor.com/commercial-door-maintenance; https://www.dasma.com/wp-content/uploads/2020/06/TDS160-Sectional-Garage-Door-Terminology.pdf",
        "source_locator": "D269 curtain/bottom-bar checks; Clopay Warnings/Inspection; D160 Astragal/Bottom Fixture",
        "source_editions": "DASMA269: Rev 2/21; issued 3/15/21; CLOPAY: Undated web page; checked 2026-09-17; DASMA160: Rev 8/17 Reaff 6/18 Rev 1/19",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S09",
        "group": "Will not move",
        "symptom_as_people_say_it": "Nothing happens when I press any button",
        "door_types": "Sectional; Rolling steel; Grille",
        "documented_context_not_ranked": "Power, stop inputs and interlocks are separate possibilities in the operator manuals.",
        "safe_observation": "Record accessible indicators and visible lock/hoist status without changing them.",
        "what_this_does_not_establish": "That the motor or control board has failed.",
        "stop_line": "Qualified diagnosis; do not bypass a lock/interlock or open an electrical enclosure.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "LM-L5; MAN-070E; GENIE-TC",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf; https://manaras.com/book1120.pdf; https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "LM p. 37 no-response troubleshooting; MAN Table 1 D9; GEN 57, 60",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text; MAN-070E: BOOK1120 REV 8, 2026/07/16; GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S10",
        "group": "Will not move",
        "symptom_as_people_say_it": "Motor hums or buzzes, door does not move",
        "door_types": "Sectional; Rolling steel",
        "documented_context_not_ranked": "A hum or click does not establish the supply condition or the failed component.",
        "safe_observation": "Record the sound and command already observed, without repeating the attempt or touching the motor.",
        "what_this_does_not_establish": "That the capacitor failed, or that the door can be forced open.",
        "stop_line": "Stop repeated attempts; qualified electrical/mechanical assessment.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "LM-L5; GENIE-TC",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf; https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "LM pp. 37–38; GEN 50, 69; sound-to-diagnosis boundary is editorial",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text; GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S11",
        "group": "Will not move",
        "symptom_as_people_say_it": "Motor runs normally, door does not move",
        "door_types": "Sectional; Rolling steel",
        "documented_context_not_ranked": "Drive connection, clutch and door movement require an equipment-specific check.",
        "safe_observation": "Record whether a motor sound was heard and whether any door movement was seen.",
        "what_this_does_not_establish": "Which drive part failed.",
        "stop_line": "Do not jog the operator, remove guards or watch exposed drive parts.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "LM-L5; CLOPAY",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf; https://www.clopaydoor.com/commercial-door-maintenance",
        "source_locator": "LM p. 37 motor/door troubleshooting; Clopay Warnings",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text; CLOPAY: Undated web page; checked 2026-09-17",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S12",
        "group": "Will not move",
        "symptom_as_people_say_it": "Moves about a foot, stops, and after that only constant pressure works",
        "door_types": "Sectional; Rolling steel",
        "documented_context_not_ranked": "On the checked LiftMaster platform, loss of opening motion feedback can produce this behaviour.",
        "safe_observation": "Record the distance already observed and the accessible maintenance-light pattern.",
        "what_this_does_not_establish": "That the RPM sensor, clutch or board is definitely defective.",
        "stop_line": "Trained assessment; do not reproduce the motion or relearn feedback yourself.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "LM-L5",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "Printed p. 37 movement-about-a-foot entry; p. 38 E2",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S13",
        "group": "Will not move",
        "symptom_as_people_say_it": "Stops most of the way, and a second press finishes it",
        "door_types": "Sectional; Rolling steel",
        "documented_context_not_ranked": "Maximum run time is one documented explanation, not a diagnosis from a second successful press.",
        "safe_observation": "Record the original sequence and any run-timer code.",
        "what_this_does_not_establish": "That increasing the timer would fix the underlying problem.",
        "stop_line": "Do not time repeated cycles or change the timer to overcome a fault.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "LM-L5; MAN-070E; GENIE-TC",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf; https://manaras.com/book1120.pdf; https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "LM p. 34 MRT/p. 38 E3; MAN p. 17 MRT; GEN 4B, 51, 52",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text; MAN-070E: BOOK1120 REV 8, 2026/07/16; GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S14",
        "group": "Will not move",
        "symptom_as_people_say_it": "Opens partway and stops at the same height every time",
        "door_types": "Sectional; Rolling steel",
        "documented_context_not_ranked": "A programmed intermediate stop is possible; a newly shortened opening still needs investigation.",
        "safe_observation": "Compare the observed stopping position with posted instructions or previous records.",
        "what_this_does_not_establish": "That a mid-stop was intentionally programmed, or that the installation is healthy.",
        "stop_line": "Do not change settings to mask a new travel problem.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "LM-L5; MAN-070E; GENIE-TC; MIC-SMART",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf; https://manaras.com/book1120.pdf; https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf; https://ismartgate.com/manuals/Micanan_Pro-J_manual.pdf",
        "source_locator": "LM mid-stop section; MAN Features Programming/Mid-Stop; GEN 3E; MIC p. 20 Mid-Stop",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text; MAN-070E: BOOK1120 REV 8, 2026/07/16; GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2; MIC-SMART: August 2010",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S15",
        "group": "Counterbalance",
        "symptom_as_people_say_it": "Loud bang, and now the door is far too heavy to lift",
        "door_types": "Sectional; Rolling steel; Grille",
        "documented_context_not_ranked": "A bang and changed lifting behaviour warrant inspection of the counterbalance and lifting hardware.",
        "safe_observation": "Record the sound and any break or spring gap visible from a safe position.",
        "what_this_does_not_establish": "Which component broke, or that remaining hardware can support the door.",
        "stop_line": "Stop use; no manual lift, release or spring/cable work.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "CLOPAY; DASMA160",
        "source_urls": "https://www.clopaydoor.com/commercial-door-maintenance; https://www.dasma.com/wp-content/uploads/2020/06/TDS160-Sectional-Garage-Door-Terminology.pdf",
        "source_locator": "Clopay Warnings/Inspection; D160 Torsion Spring/Counterbalance",
        "source_editions": "CLOPAY: Undated web page; checked 2026-09-17; DASMA160: Rev 8/17 Reaff 6/18 Rev 1/19",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S16",
        "group": "Counterbalance",
        "symptom_as_people_say_it": "Hangs crooked or at an angle in the opening",
        "door_types": "Sectional; Rolling steel",
        "documented_context_not_ranked": "Crooked travel can involve the door, guides/tracks or lifting hardware.",
        "safe_observation": "Record visible position and damage from outside the opening.",
        "what_this_does_not_establish": "That a single cable replacement is sufficient.",
        "stop_line": "Keep clear; no cycling, lifting or cable/drum adjustments.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "CLOPAY; DASMA269",
        "source_urls": "https://www.clopaydoor.com/commercial-door-maintenance; https://www.dasma.com/wp-content/uploads/2021/03/TDS269-l.pdf",
        "source_locator": "Clopay Warnings/Inspection; D269 curtain/guides/bottom-bar checks",
        "source_editions": "CLOPAY: Undated web page; checked 2026-09-17; DASMA269: Rev 2/21; issued 3/15/21",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S17",
        "group": "Counterbalance",
        "symptom_as_people_say_it": "A cable is off the drum or hanging slack",
        "door_types": "Sectional",
        "documented_context_not_ranked": "Jackshaft applications need suitable cable tension; the door/application must be assessed together.",
        "safe_observation": "Record whether slack was visible and identify the operator from records.",
        "what_this_does_not_establish": "Why the cable went slack or what setting should change.",
        "stop_line": "Stop use; no cable reseating or improvised added weights/springs.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "DASMA1501; CLOPAY",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2022/12/TDS1501.pdf; https://www.clopaydoor.com/commercial-door-maintenance",
        "source_locator": "D1501 standard-lift jackshaft application/cable tension; Clopay Warnings",
        "source_editions": "DASMA1501: 12/08/22; CLOPAY: Undated web page; checked 2026-09-17",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S18",
        "group": "Counterbalance",
        "symptom_as_people_say_it": "Drifts down by itself after being stopped partway",
        "door_types": "Sectional; Rolling steel",
        "documented_context_not_ranked": "A door that descends unexpectedly needs assessment of its support and operating system.",
        "safe_observation": "Report the drift already observed and its position; keep the opening clear.",
        "what_this_does_not_establish": "Whether the spring, brake or another component is responsible.",
        "stop_line": "Stop use; do not stand under it or test its holding ability again.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "CLOPAY; DASMA269",
        "source_urls": "https://www.clopaydoor.com/commercial-door-maintenance; https://www.dasma.com/wp-content/uploads/2021/03/TDS269-l.pdf",
        "source_locator": "Clopay Check Operation/Warnings; D269 performance criteria",
        "source_editions": "CLOPAY: Undated web page; checked 2026-09-17; DASMA269: Rev 2/21; issued 3/15/21",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S19",
        "group": "Counterbalance",
        "symptom_as_people_say_it": "Will not stay open when released by hand",
        "door_types": "Sectional",
        "documented_context_not_ranked": "A balance problem is possible; added weight can change a sectional door’s counterbalance needs.",
        "safe_observation": "Report the manual behaviour already observed and any known added material or recent work.",
        "what_this_does_not_establish": "That the springs simply need more turns.",
        "stop_line": "Do not disconnect, lift or rebalance the suspect door.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "CLOPAY; DASMA176",
        "source_urls": "https://www.clopaydoor.com/commercial-door-maintenance; https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/CommercialResidential/TDS176.pdf",
        "source_locator": "Clopay Check Operation; D176 p. 1",
        "source_editions": "CLOPAY: Undated web page; checked 2026-09-17; DASMA176: 1/30/06; Rev 8/08; reaffirmed 6/19",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S20",
        "group": "Counterbalance",
        "symptom_as_people_say_it": "Very hard to lift by hand with the operator disconnected",
        "door_types": "Sectional; Rolling steel",
        "documented_context_not_ranked": "Hard manual movement needs a door-system assessment, not greater pulling force.",
        "safe_observation": "Record any difficulty already encountered; do not repeat a manual test.",
        "what_this_does_not_establish": "Which component is binding.",
        "stop_line": "No release/hoist or under-door work on a suspect assembly.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "CLOPAY; DASMA269",
        "source_urls": "https://www.clopaydoor.com/commercial-door-maintenance; https://www.dasma.com/wp-content/uploads/2021/03/TDS269-l.pdf",
        "source_locator": "Clopay Check Operation/Warnings; D269 performance criteria",
        "source_editions": "CLOPAY: Undated web page; checked 2026-09-17; DASMA269: Rev 2/21; issued 3/15/21",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S21",
        "group": "Counterbalance",
        "symptom_as_people_say_it": "Bottom section is bowed and the door will not seal",
        "door_types": "Sectional",
        "documented_context_not_ranked": "Visible impact damage needs inspection of the assembly, not just the dent.",
        "safe_observation": "Photograph the visible damage from outside the travel path.",
        "what_this_does_not_establish": "Whether a section, bracket, track or complete assembly needs replacement.",
        "stop_line": "Stop use where damage affects travel or support; do not straighten components.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "CLOPAY; DASMA269",
        "source_urls": "https://www.clopaydoor.com/commercial-door-maintenance; https://www.dasma.com/wp-content/uploads/2021/03/TDS269-l.pdf",
        "source_locator": "Clopay Inspection/Warnings; D269 curtain/bottom-bar/guides",
        "source_editions": "CLOPAY: Undated web page; checked 2026-09-17; DASMA269: Rev 2/21; issued 3/15/21",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S22",
        "group": "Track and curtain",
        "symptom_as_people_say_it": "Binds or sticks partway through travel",
        "door_types": "Sectional; Rolling steel; Grille",
        "documented_context_not_ranked": "Track/guide condition and visible debris are relevant observations.",
        "safe_observation": "Note visible damage or debris without reaching into the travel path.",
        "what_this_does_not_establish": "That removing debris makes the whole assembly safe.",
        "stop_line": "Do not unjam, bend tracks or force travel.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "CLOPAY; DASMA269",
        "source_urls": "https://www.clopaydoor.com/commercial-door-maintenance; https://www.dasma.com/wp-content/uploads/2021/03/TDS269-l.pdf",
        "source_locator": "Clopay Inspection; D269 guides/curtain/performance",
        "source_editions": "CLOPAY: Undated web page; checked 2026-09-17; DASMA269: Rev 2/21; issued 3/15/21",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S23",
        "group": "Track and curtain",
        "symptom_as_people_say_it": "Came out of the track, or the rollers are off",
        "door_types": "Sectional",
        "documented_context_not_ranked": "A derailed roller or displaced section requires a trained door-system assessment.",
        "safe_observation": "Record the position without moving the door.",
        "what_this_does_not_establish": "That reseating one roller is the complete repair.",
        "stop_line": "Stop use; no cycling or reseating.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "CLOPAY",
        "source_urls": "https://www.clopaydoor.com/commercial-door-maintenance",
        "source_locator": "Warnings/Inspection; stop-use routing is editorial",
        "source_editions": "CLOPAY: Undated web page; checked 2026-09-17",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S24",
        "group": "Track and curtain",
        "symptom_as_people_say_it": "Rolling door curtain jammed in the guides",
        "door_types": "Rolling steel; Grille",
        "documented_context_not_ranked": "Rolling-door guides, curtain, endlocks and bottom bar are separate inspection points.",
        "safe_observation": "Record where it was seen to bind; inspect only externally visible damage.",
        "what_this_does_not_establish": "Which hidden part is causing the jam.",
        "stop_line": "Do not pull slats, open the hood or force the curtain.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "DASMA269; DASMA277",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2021/03/TDS269-l.pdf; https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf",
        "source_locator": "D269 guides/curtain/bottom-bar; D277 Bellmouth/Endlock",
        "source_editions": "DASMA269: Rev 2/21; issued 3/15/21; DASMA277: 9/3/03 Rev 6/20",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S25",
        "group": "Track and curtain",
        "symptom_as_people_say_it": "Grinding, shrieking or squealing while it runs",
        "door_types": "Sectional; Rolling steel",
        "documented_context_not_ranked": "A new noise is useful symptom information, not proof that one part needs lubrication.",
        "safe_observation": "Describe when the sound occurred; no repeat cycles to locate it.",
        "what_this_does_not_establish": "Which bearing, roller or drive component is responsible.",
        "stop_line": "Stop use if movement is abnormal; no guard removal or hands-on diagnosis.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "CLOPAY; DASMA269",
        "source_urls": "https://www.clopaydoor.com/commercial-door-maintenance; https://www.dasma.com/wp-content/uploads/2021/03/TDS269-l.pdf",
        "source_locator": "Clopay Inspection/Warnings; D269 performance criteria",
        "source_editions": "CLOPAY: Undated web page; checked 2026-09-17; DASMA269: Rev 2/21; issued 3/15/21",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S26",
        "group": "Track and curtain",
        "symptom_as_people_say_it": "Shudders or shakes as it travels",
        "door_types": "Sectional; Rolling steel",
        "documented_context_not_ranked": "Shaking or jerking requires inspection of the door and operator together.",
        "safe_observation": "Report the motion already observed and any visible wear or damage.",
        "what_this_does_not_establish": "That the motor alone is at fault.",
        "stop_line": "Do not run a complete cycle to demonstrate it.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "CLOPAY; DASMA269",
        "source_urls": "https://www.clopaydoor.com/commercial-door-maintenance; https://www.dasma.com/wp-content/uploads/2021/03/TDS269-l.pdf",
        "source_locator": "Clopay Inspection; D269 performance criteria",
        "source_editions": "CLOPAY: Undated web page; checked 2026-09-17; DASMA269: Rev 2/21; issued 3/15/21",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S27",
        "group": "Track and curtain",
        "symptom_as_people_say_it": "Slats have shifted sideways on a rolling door",
        "door_types": "Rolling steel",
        "documented_context_not_ranked": "Endlocks restrain lateral movement of rolling-steel slats; the complete curtain/guides need inspection.",
        "safe_observation": "Photograph displaced slats only as they already sit, from a safe position.",
        "what_this_does_not_establish": "That an endlock is the only failed part.",
        "stop_line": "Do not reposition the curtain or remove the hood.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "DASMA277; DASMA269",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf; https://www.dasma.com/wp-content/uploads/2021/03/TDS269-l.pdf",
        "source_locator": "D277 Endlock; D269 curtain/endlock inspection",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20; DASMA269: Rev 2/21; issued 3/15/21",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S28",
        "group": "Electrical and control",
        "symptom_as_people_say_it": "Breaker trips when the door runs",
        "door_types": "Sectional; Rolling steel",
        "documented_context_not_ranked": "Electrical protective-device trips and a motor-overheat message are different evidence.",
        "safe_observation": "Record which protective device tripped and any message already seen.",
        "what_this_does_not_establish": "That resetting it, waiting or replacing a motor resolves the cause.",
        "stop_line": "Do not repeatedly reset; qualified electrical assessment. For smoke, fire or sparking, follow the site emergency procedure.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "OSHA333; LM-L5; GENIE-TC",
        "source_urls": "https://www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.333; https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf; https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "OSHA333(b)(2), (c)(2); LM E8; GEN 50/69",
        "source_editions": "OSHA333: Federal rule text checked 2026-09-17; LM-L5: 45-page manufacturer manual; date not stated in inspected text; GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S29",
        "group": "Electrical and control",
        "symptom_as_people_say_it": "Runs the wrong direction after an electrical repair",
        "door_types": "Sectional; Rolling steel",
        "documented_context_not_ranked": "Wrong direction after work requires verification of the installed electrical/mechanical setup.",
        "safe_observation": "Record the command, direction already observed and what work preceded it.",
        "what_this_does_not_establish": "That swapping two wires is the correct or safe fix.",
        "stop_line": "Stop use; no phase changes, jumper changes or limit resets by the reader.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "MAN-070E; LM-L5; GENIE-TC",
        "source_urls": "https://manaras.com/book1120.pdf; https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf; https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "MAN Table 2 wrong handing; LM E10; GEN 5A/5B",
        "source_editions": "MAN-070E: BOOK1120 REV 8, 2026/07/16; LM-L5: 45-page manufacturer manual; date not stated in inspected text; GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S30",
        "group": "Electrical and control",
        "symptom_as_people_say_it": "A light on the operator or wall station is flashing a pattern",
        "door_types": "Sectional; Rolling steel; Grille",
        "documented_context_not_ranked": "Indicators can describe normal status, maintenance or a fault, depending on the device and platform.",
        "safe_observation": "Write down the complete accessible message, light label, pattern and model.",
        "what_this_does_not_establish": "That a generic blink chart applies.",
        "stop_line": "No cover removal or clearing the message just to see whether it returns.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "LM-L5; MAN-070E; GENIE-TC; MIC-SMART",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf; https://manaras.com/book1120.pdf; https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf; https://ismartgate.com/manuals/Micanan_Pro-J_manual.pdf",
        "source_locator": "LM pp. 36–39; MAN Tables 1–2; GEN run/error headings; MIC p. 22 status table",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text; MAN-070E: BOOK1120 REV 8, 2026/07/16; GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2; MIC-SMART: August 2010",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S31",
        "group": "Electrical and control",
        "symptom_as_people_say_it": "Wall station does nothing, but the buttons on the board work",
        "door_types": "Sectional; Rolling steel",
        "documented_context_not_ranked": "A difference between local control and an earlier board-control test can point to a command-path issue.",
        "safe_observation": "Use only a qualified person’s existing report; do not open the box or press board controls.",
        "what_this_does_not_establish": "That the stop circuit or entire wall station is certainly defective.",
        "stop_line": "Qualified electrical/control assessment.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "LM-L5; GENIE-TC",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf; https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "LM p. 37 Stop LED troubleshooting; GEN 60",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text; GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S32",
        "group": "Electrical and control",
        "symptom_as_people_say_it": "Opens or closes by itself",
        "door_types": "Sectional; Rolling steel; Grille",
        "documented_context_not_ranked": "Automatic closing can be a configured timer function; unexplained movement is not a normal-status diagnosis.",
        "safe_observation": "Compare previously observed behaviour with posted operating instructions and existing records.",
        "what_this_does_not_establish": "That a timer explains every uncommanded movement.",
        "stop_line": "Keep clear; stop use of unexplained operation and have it assessed.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "LM-L5; MAN-070E; GENIE-TC; MIC-SMART",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf; https://manaras.com/book1120.pdf; https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf; https://ismartgate.com/manuals/Micanan_Pro-J_manual.pdf",
        "source_locator": "LM T/TS/FSTS; MAN p. 16 T/TS; GEN 2A; MIC pp. 18–19",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text; MAN-070E: BOOK1120 REV 8, 2026/07/16; GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2; MIC-SMART: August 2010",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S33",
        "group": "Safety devices",
        "symptom_as_people_say_it": "The photo eye light is blinking",
        "door_types": "Sectional; Rolling steel; Grille",
        "documented_context_not_ranked": "Sensor indication meanings depend on the exact sensor/controller; beam-height rules apply to identified protection devices.",
        "safe_observation": "Record the device label and light pattern from a safe position.",
        "what_this_does_not_establish": "That one colour means healthy across brands, or that a high vehicle detector is the primary protection device.",
        "stop_line": "No sensor relocation, wiring or bypassing.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "DASMA382; MAN-070E",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2022/06/TDS382.pdf; https://manaras.com/book1120.pdf",
        "source_locator": "D382 pp. 1–2; MAN §1.4/Table 1",
        "source_editions": "DASMA382: REV 05/22/22 (orig 6/26/17); MAN-070E: BOOK1120 REV 8, 2026/07/16",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S34",
        "group": "Safety devices",
        "symptom_as_people_say_it": "The sensing edge does nothing when I press it",
        "door_types": "Sectional; Rolling steel",
        "documented_context_not_ranked": "A closing edge that fails its specified test needs assessment; a photoeye is a different device.",
        "safe_observation": "Record the failed test reported by designated personnel; do not perform an improvised object test.",
        "what_this_does_not_establish": "That another working sensor replaces the failed device.",
        "stop_line": "Stop use pending assessment under the exact manufacturer procedure.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "DASMA269; DASMA382",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2021/03/TDS269-l.pdf; https://www.dasma.com/wp-content/uploads/2022/06/TDS382.pdf",
        "source_locator": "D269 sensing-edge check; D382 primary/secondary protection",
        "source_editions": "DASMA269: Rev 2/21; issued 3/15/21; DASMA382: REV 05/22/22 (orig 6/26/17)",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S35",
        "group": "Safety devices",
        "symptom_as_people_say_it": "The sensing edge stops the door on the way UP",
        "door_types": "Sectional; Rolling steel",
        "documented_context_not_ranked": "For the closing-edge arrangement discussed by DASMA, reversing on opening is an installation concern.",
        "safe_observation": "Report that behaviour if already observed; do not repeat the test.",
        "what_this_does_not_establish": "That the wiring error has been identified without inspection.",
        "stop_line": "Qualified assessment; no wiring changes.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "DASMA375",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/OperatorElectronics/TDS375.pdf",
        "source_locator": "p. 2 reversing-device operation",
        "source_editions": "DASMA375: 2/8/06 Rev 12-13 Reaff 3-17",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S36",
        "group": "Fire doors",
        "symptom_as_people_say_it": "The rolling door came down on its own and will not go back up",
        "door_types": "Rolling fire door",
        "documented_context_not_ranked": "A fire door may close following a release signal; unexpected closure still needs the cause established.",
        "safe_observation": "Follow the site alarm response; record any known alarm, release or power event.",
        "what_this_does_not_establish": "That the door worked correctly or is merely ready to reset.",
        "stop_line": "No manual reopening, reset or release-device adjustment; trained fire-door assessment.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "DASMA277; DASMA299; GENIE-TC",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf; https://www.dasma.com/wp-content/uploads/2023/04/TDS299.pdf; https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "D277 Automatic Closing Device; D299 pp. 1–2; GEN Fire Door Module p. 10",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20; DASMA299: 4/13/23; discusses NFPA 80-2022; GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S37",
        "group": "Fire doors",
        "symptom_as_people_say_it": "A chain hanging with a weight and a small soldered metal link",
        "door_types": "Rolling fire door; Sliding fire door",
        "documented_context_not_ranked": "Fire-release hardware is a clue, not a substitute for the door label and equipment records.",
        "safe_observation": "Check labels/records that are safely accessible; do not open the hood to identify components.",
        "what_this_does_not_establish": "The door’s rating, certification or exact type from one piece of hardware.",
        "stop_line": "Treat suspected fire-protection equipment as specialist work until identified.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "DASMA277; DASMA267",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf; https://www.dasma.com/wp-content/uploads/2025/04/TDS267.pdf",
        "source_locator": "D277 named fire terms and governor; D267 RDD-200/RDD-203/RDD-205",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20; DASMA267: Rev 1/24",
        "last_verified": "2026-09-17"
      },
      {
        "symptom_id": "S38",
        "group": "Fire doors",
        "symptom_as_people_say_it": "A fire door operator is showing a trouble light",
        "door_types": "Rolling fire door",
        "documented_context_not_ranked": "Fire-module messages can identify a required test or a circuit/power problem.",
        "safe_observation": "Record the exact message and module model without clearing it.",
        "what_this_does_not_establish": "That a test-required notice proves the assembly is fault-free.",
        "stop_line": "Trained rolling fire-door personnel; no test-key or reset instructions here.",
        "evidence_type": "Source-grounded synthesis; observations and stop lines are editorial",
        "source_keys": "GENIE-TC; DASMA299",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf; https://www.dasma.com/wp-content/uploads/2023/04/TDS299.pdf",
        "source_locator": "GEN p. 10, including trouble code 15; D299 pp. 1–2",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2; DASMA299: 4/13/23; discusses NFPA 80-2022",
        "last_verified": "2026-09-17"
      }
    ],
    "operator-mode-crosswalk": [
      {
        "mode_code": "C2",
        "plain_english": "Tap to open or stop. Hold the button to close.",
        "what_happens_when_the_close_button_is_released": "LiftMaster: the door stops. Manaras: the door stops, and an entrapment device activating reverses it while closing.",
        "monitored_entrapment_device": "Manufacturer/installation-specific; held-button mode does not certify the installation.",
        "liftmaster_logic_5_0": "Dial C2.",
        "manaras_board_070e": "Selector position 0.",
        "micanan_smart_10_0": "C2 stops when CLOSE is released; Smart 10.0 description, not a relay-wiring instruction.",
        "genie_gcl_gcx_equivalent": "Comparable button-contact pattern: momentary open, held close. Not a verified full mode equivalence.",
        "source_keys": "LM-L5; MAN-070E; MIC-SMART; GENIE-TC",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf; https://manaras.com/book1120.pdf; https://ismartgate.com/manuals/Micanan_Pro-J_manual.pdf; https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "LM printed pp. 28–29 C2; MAN p. 16 Run Mode Settings; MIC pp. 17–20 C2; GEN codes 3A, 61, 62 (limited terminology comparison only)",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text; MAN-070E: BOOK1120 REV 8, 2026/07/16; MIC-SMART: August 2010; GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17",
        "evidence_type": "Manufacturer-reported descriptions; cross-brand comparison editorial; no certified equivalence"
      },
      {
        "mode_code": "B2",
        "plain_english": "Tap for open, close and stop. Hands-free closing.",
        "what_happens_when_the_close_button_is_released": "Not applicable - closing is momentary",
        "monitored_entrapment_device": "LM/MIC require documented monitored protection for the named configurations. MAN §1.4 requires entrapment protection but includes non-monitored examples; this is not a universal compliance crosswalk.",
        "liftmaster_logic_5_0": "Dial B2. Mid stop available.",
        "manaras_board_070e": "Selector position 1.",
        "micanan_smart_10_0": "B2; required primary monitored device for momentary closing in this manual.",
        "genie_gcl_gcx_equivalent": "Momentary/held-contact terminology exists, but this chart does not certify a B2-equivalent installation.",
        "source_keys": "LM-L5; MAN-070E; MIC-SMART; GENIE-TC",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf; https://manaras.com/book1120.pdf; https://ismartgate.com/manuals/Micanan_Pro-J_manual.pdf; https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "LM printed pp. 28–29 B2; MAN p. 16 Run Mode Settings; MIC pp. 17–20 B2; GEN codes 3A, 61, 62 (limited terminology comparison only)",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text; MAN-070E: BOOK1120 REV 8, 2026/07/16; MIC-SMART: August 2010; GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17",
        "evidence_type": "Manufacturer-reported descriptions; cross-brand comparison editorial; no certified equivalence"
      },
      {
        "mode_code": "D1",
        "plain_english": "Hold the button to open AND to close.",
        "what_happens_when_the_close_button_is_released": "The door stops. On Manaras an entrapment device activating stops the door rather than reversing it.",
        "monitored_entrapment_device": "Follow the exact manufacturer and installed-system requirements.",
        "liftmaster_logic_5_0": "Dial D1.",
        "manaras_board_070e": "Selector position 2. Safety activation stops closing in this mode.",
        "micanan_smart_10_0": "D1; hold OPEN and CLOSE; releasing either stops movement.",
        "genie_gcl_gcx_equivalent": "Comparable button-contact pattern: held open and held close. Not a complete mode equivalence.",
        "source_keys": "LM-L5; MAN-070E; MIC-SMART; GENIE-TC",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf; https://manaras.com/book1120.pdf; https://ismartgate.com/manuals/Micanan_Pro-J_manual.pdf; https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "LM printed pp. 28–29 D1; MAN p. 16 Run Mode Settings; MIC pp. 17–20 D1; GEN codes 3A, 61, 62 (limited terminology comparison only)",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text; MAN-070E: BOOK1120 REV 8, 2026/07/16; MIC-SMART: August 2010; GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17",
        "evidence_type": "Manufacturer-reported descriptions; cross-brand comparison editorial; no certified equivalence"
      },
      {
        "mode_code": "E2",
        "plain_english": "Tap to open. Hold to close, and letting go sends it back up.",
        "what_happens_when_the_close_button_is_released": "The door reverses to fully open - the roll-back feature",
        "monitored_entrapment_device": "Follow the exact manufacturer and installed-system requirements.",
        "liftmaster_logic_5_0": "Dial E2; three-button station.",
        "manaras_board_070e": "Selector position 3.",
        "micanan_smart_10_0": "E2 includes reversal on release of CLOSE.",
        "genie_gcl_gcx_equivalent": "No exact E2 roll-back equivalence verified. Code 3A alone does not establish one.",
        "source_keys": "LM-L5; MAN-070E; MIC-SMART; GENIE-TC",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf; https://manaras.com/book1120.pdf; https://ismartgate.com/manuals/Micanan_Pro-J_manual.pdf; https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "LM printed pp. 28–29 E2; MAN p. 16 Run Mode Settings; MIC pp. 17–20 E2; GEN codes 3A, 61, 62 (limited terminology comparison only)",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text; MAN-070E: BOOK1120 REV 8, 2026/07/16; MIC-SMART: August 2010; GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17",
        "evidence_type": "Manufacturer-reported descriptions; cross-brand comparison editorial; no certified equivalence"
      },
      {
        "mode_code": "T",
        "plain_english": "Tap for open, close and stop, plus a timer that closes the door on its own.",
        "what_happens_when_the_close_button_is_released": "Not applicable",
        "monitored_entrapment_device": "LM/MIC require documented monitored protection for the named configurations. MAN §1.4 requires entrapment protection but includes non-monitored examples; this is not a universal compliance crosswalk.",
        "liftmaster_logic_5_0": "Dial T; see the manual’s timer conditions.",
        "manaras_board_070e": "Selector position 4; safety activation can disable timer closing until fully closed.",
        "micanan_smart_10_0": "T: STOP and safety activation can disable the timer; separate delay-on-close accessory is disabled in T.",
        "genie_gcl_gcx_equivalent": "TCM is a timer module; code 61 concerns disabled timed closing. No exact T equivalence verified.",
        "source_keys": "LM-L5; MAN-070E; MIC-SMART; GENIE-TC",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf; https://manaras.com/book1120.pdf; https://ismartgate.com/manuals/Micanan_Pro-J_manual.pdf; https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "LM printed pp. 28–29 T; MAN p. 16 Run Mode Settings; MIC pp. 17–20 T; GEN codes 3A, 61, 62 (limited terminology comparison only)",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text; MAN-070E: BOOK1120 REV 8, 2026/07/16; MIC-SMART: August 2010; GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17",
        "evidence_type": "Manufacturer-reported descriptions; cross-brand comparison editorial; no certified equivalence"
      },
      {
        "mode_code": "TS",
        "plain_english": "A timer-closing mode whose restart and STOP behaviour differs by manufacturer.",
        "what_happens_when_the_close_button_is_released": "Not applicable",
        "monitored_entrapment_device": "LM/MIC require documented monitored protection for the named configurations. MAN §1.4 requires entrapment protection but includes non-monitored examples; this is not a universal compliance crosswalk.",
        "liftmaster_logic_5_0": "Dial TS; STOP does not disable the timer.",
        "manaras_board_070e": "Selector position 5; timer refreshes after the specified stop/hoist/power conditions.",
        "micanan_smart_10_0": "TS: STOP disables the timer; safety activation refreshes it. Delay-on-close is an optional apartment-board function.",
        "genie_gcl_gcx_equivalent": "No exact TS equivalence verified.",
        "source_keys": "LM-L5; MAN-070E; MIC-SMART; GENIE-TC",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf; https://manaras.com/book1120.pdf; https://ismartgate.com/manuals/Micanan_Pro-J_manual.pdf; https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "LM printed pp. 28–29 TS; MAN p. 16 Run Mode Settings; MIC pp. 17–20 TS; GEN codes 3A, 61, 62 (limited terminology comparison only)",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text; MAN-070E: BOOK1120 REV 8, 2026/07/16; MIC-SMART: August 2010; GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17",
        "evidence_type": "Manufacturer-reported descriptions; cross-brand comparison editorial; no certified equivalence"
      },
      {
        "mode_code": "FSTS",
        "plain_english": "One button opens fully and starts the timer, then the door behaves like TS until it closes.",
        "what_happens_when_the_close_button_is_released": "Not applicable",
        "monitored_entrapment_device": "LiftMaster requires its documented monitored protection for this wiring type.",
        "liftmaster_logic_5_0": "Dial FSTS.",
        "manaras_board_070e": "Not listed in the checked BOARD 070E mode table.",
        "micanan_smart_10_0": "Not listed in the checked Smart 10.0 manual.",
        "genie_gcl_gcx_equivalent": "No equivalent verified.",
        "source_keys": "LM-L5; MAN-070E; MIC-SMART; GENIE-TC",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf; https://manaras.com/book1120.pdf; https://ismartgate.com/manuals/Micanan_Pro-J_manual.pdf; https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "LM printed pp. 28–29 FSTS; MAN p. 16 Run Mode Settings; MIC pp. 17–20 FSTS; GEN codes 3A, 61, 62 (limited terminology comparison only)",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text; MAN-070E: BOOK1120 REV 8, 2026/07/16; MIC-SMART: August 2010; GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17",
        "evidence_type": "Manufacturer-reported descriptions; cross-brand comparison editorial; no certified equivalence"
      }
    ],
    "operator-fault-codes": [
      {
        "brand": "LiftMaster",
        "control_platform": "Logic 5.0 — T, APT, H, J, HJ, GH, GT manual",
        "indicator_type": "Blink count on the maintenance LED",
        "code_or_pattern": "1 blink",
        "what_the_operator_is_reporting": "Maintenance interval reached, by cycles or by months",
        "effect_on_the_door": "Maintenance indication does not itself inhibit operation; it is not a safety clearance.",
        "what_to_report_or_have_assessed": "Report the maintenance indication and existing service history; do not reset a counter instead of arranging maintenance.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "LM-L5",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "Printed p. 38 error table; 1 blink",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "LiftMaster",
        "control_platform": "Logic 5.0 — T, APT, H, J, HJ, GH, GT manual",
        "indicator_type": "Blink count",
        "code_or_pattern": "2 blinks",
        "what_the_operator_is_reporting": "No motion feedback while opening",
        "effect_on_the_door": "Door responds to constant pressure only",
        "what_to_report_or_have_assessed": "Report the opening-motion indication. The manual distinguishes feedback, clutch and drive checks; it does not prove the sensor failed.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "LM-L5",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "Printed p. 38 error table; 2 blinks",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "LiftMaster",
        "control_platform": "Logic 5.0 — T, APT, H, J, HJ, GH, GT manual",
        "indicator_type": "Blink count",
        "code_or_pattern": "3 blinks",
        "what_the_operator_is_reporting": "Maximum run timer expired",
        "effect_on_the_door": "Door stops before reaching a limit",
        "what_to_report_or_have_assessed": "Report the point where travel stopped. The cause of a timed-out run needs assessment before settings are changed.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "LM-L5",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "Printed p. 38 error table; 3 blinks",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "LiftMaster",
        "control_platform": "Logic 5.0 — T, APT, H, J, HJ, GH, GT manual",
        "indicator_type": "Blink count",
        "code_or_pattern": "4 blinks",
        "what_the_operator_is_reporting": "Obstruction sensed, or motion feedback lost while closing",
        "effect_on_the_door": "Door reverses to open",
        "what_to_report_or_have_assessed": "Report the closing obstruction/motion indication; do not repeat the reversal as a test.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "LM-L5",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "Printed p. 38 error table; 4 blinks",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "LiftMaster",
        "control_platform": "Logic 5.0 — T, APT, H, J, HJ, GH, GT manual",
        "indicator_type": "Blink count",
        "code_or_pattern": "5 blinks",
        "what_the_operator_is_reporting": "A button has been held for more than two minutes",
        "effect_on_the_door": "That button is ignored",
        "what_to_report_or_have_assessed": "Identify which control was already observed active. Do not force, jumper or bypass it.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "LM-L5",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "Printed p. 38 error table; 5 blinks",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "LiftMaster",
        "control_platform": "Logic 5.0 — T, APT, H, J, HJ, GH, GT manual",
        "indicator_type": "Blink count",
        "code_or_pattern": "6 blinks",
        "what_the_operator_is_reporting": "Unsupported option card fitted",
        "effect_on_the_door": "Option card does not work",
        "what_to_report_or_have_assessed": "Have the installed option card and controller compatibility checked; no live-board access.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "LM-L5",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "Printed p. 38 error table; 6 blinks",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "LiftMaster",
        "control_platform": "Logic 5.0 — T, APT, H, J, HJ, GH, GT manual",
        "indicator_type": "Blink count",
        "code_or_pattern": "7 blinks",
        "what_the_operator_is_reporting": "Monitored entrapment device faulted or removed for more than two minutes",
        "effect_on_the_door": "Manual describes a five-second held-button closing override; this reference does not recommend using it.",
        "what_to_report_or_have_assessed": "Stop relying on the override and report E7 and the protection-device indication. A blockage, removal and defective component are not the same diagnosis.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "LM-L5",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "Printed p. 38 error table; 7 blinks",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "LiftMaster",
        "control_platform": "Logic 5.0 — T, APT, H, J, HJ, GH, GT manual",
        "indicator_type": "Blink count",
        "code_or_pattern": "8 blinks",
        "what_the_operator_is_reporting": "Brownout detected",
        "effect_on_the_door": "Operator runs only while enough power is present",
        "what_to_report_or_have_assessed": "Report the low-voltage indication for qualified supply/control-power assessment.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "LM-L5",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "Printed p. 38 error table; 8 blinks",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "LiftMaster",
        "control_platform": "Logic 5.0 — T, APT, H, J, HJ, GH, GT manual",
        "indicator_type": "Blink count",
        "code_or_pattern": "Flash at the start of movement",
        "what_the_operator_is_reporting": "Motor movement at an invalid time",
        "effect_on_the_door": "The manual describes five operations before held-button-only operation; do not run those operations as a test.",
        "what_to_report_or_have_assessed": "Report when the unexpected-motion indication appeared; do not run extra operations to clear it.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "LM-L5",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "Printed p. 38 error table; Flash at the start of movement",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "LiftMaster",
        "control_platform": "Logic 5.0 — T, APT, H, J, HJ, GH, GT manual",
        "indicator_type": "Blink count",
        "code_or_pattern": "10 blinks",
        "what_the_operator_is_reporting": "Motor phase jumper moved outside programming mode",
        "effect_on_the_door": "The phase does not change",
        "what_to_report_or_have_assessed": "Report any recent electrical work. Phase/configuration assessment belongs to qualified personnel.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "LM-L5",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "Printed p. 38 error table; 10 blinks",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "LiftMaster",
        "control_platform": "Logic 5.0 — T, APT, H, J, HJ, GH, GT manual",
        "indicator_type": "Radio LED",
        "code_or_pattern": "Quick flash",
        "what_the_operator_is_reporting": "Remote not learned",
        "effect_on_the_door": "No response from that remote",
        "what_to_report_or_have_assessed": "Record the remote model and whether it previously worked. Use the matching commercial programming instructions through authorised personnel.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "LM-L5",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "Printed p. 39 radio troubleshooting; Quick flash",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "LiftMaster",
        "control_platform": "Logic 5.0 — T, APT, H, J, HJ, GH, GT manual",
        "indicator_type": "Radio LED",
        "code_or_pattern": "No activity",
        "what_the_operator_is_reporting": "Remote not recognised - weak battery, interference, wrong type, or antenna fault",
        "effect_on_the_door": "No response",
        "what_to_report_or_have_assessed": "Record remote model and previously observed range; the indication alone does not distinguish the listed possibilities.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "LM-L5",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "Printed p. 39 radio troubleshooting; No activity",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "LiftMaster",
        "control_platform": "Logic 5.0 — T, APT, H, J, HJ, GH, GT manual",
        "indicator_type": "Radio LED",
        "code_or_pattern": "2 blinks",
        "what_the_operator_is_reporting": "Receiver memory full",
        "effect_on_the_door": "New remote cannot be learned",
        "what_to_report_or_have_assessed": "Report the learning-state indication. Do not erase all stored remotes to troubleshoot one remote.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "LM-L5",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "Printed p. 39 radio troubleshooting; 2 blinks",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "LiftMaster",
        "control_platform": "Logic 5.0 — T, APT, H, J, HJ, GH, GT manual",
        "indicator_type": "Radio LED",
        "code_or_pattern": "3 blinks",
        "what_the_operator_is_reporting": "During radio learning, the remote already has a stored function",
        "effect_on_the_door": "The requested learning operation is not completed; this is not a failed-receiver diagnosis.",
        "what_to_report_or_have_assessed": "Report the remote and learning operation; existing programming is different from a defective receiver.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "LM-L5",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "Printed p. 39 radio troubleshooting; 3 blinks",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "LiftMaster",
        "control_platform": "Logic 5.0 — T, APT, H, J, HJ, GH, GT manual",
        "indicator_type": "Status LED",
        "code_or_pattern": "Entrapment LED flashing",
        "what_the_operator_is_reporting": "LMEP indication calls for assessment of sensor connection/activation or learned-device status",
        "effect_on_the_door": "Closing can be restricted; radio-held closing has additional conditions in the same manual.",
        "what_to_report_or_have_assessed": "Report the LMEP indication; do not disconnect or unlearn a protection device.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "LM-L5",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "Printed p. 36 diagnostic chart and p. 37 troubleshooting; Entrapment LED flashing",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "LiftMaster",
        "control_platform": "Logic 5.0 — T, APT, H, J, HJ, GH, GT manual",
        "indicator_type": "Status LED",
        "code_or_pattern": "Entrapment LED off",
        "what_the_operator_is_reporting": "No entrapment sensors learned",
        "effect_on_the_door": "Automatic/momentary closing is restricted; the manual separately limits held-button radio closing.",
        "what_to_report_or_have_assessed": "Have the installed protection and intended operating mode assessed; an unlit LED does not prove no device was ever fitted.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "LM-L5",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "Printed p. 36 diagnostic chart and p. 37 troubleshooting; Entrapment LED off",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "LiftMaster",
        "control_platform": "Logic 5.0 — T, APT, H, J, HJ, GH, GT manual",
        "indicator_type": "Status LED",
        "code_or_pattern": "Stop LED off",
        "what_the_operator_is_reporting": "Stop circuit open, or an interlock is active",
        "effect_on_the_door": "The board ignores the wall station",
        "what_to_report_or_have_assessed": "Report the labelled STOP light and any already known hoist/disconnect condition; do not bypass an interlock.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "LM-L5",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "Printed p. 36 diagnostic chart and p. 37 troubleshooting; Stop LED off",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Manaras-Opera",
        "control_platform": "BOARD 070E",
        "indicator_type": "Status LED",
        "code_or_pattern": "D1 green on",
        "what_the_operator_is_reporting": "24 VDC present",
        "effect_on_the_door": "Status indication only; it does not establish the whole installation is safe.",
        "what_to_report_or_have_assessed": "Record unexpected behaviour separately. This indication alone is not a fault diagnosis or a return-to-service decision.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "MAN-070E",
        "source_urls": "https://manaras.com/book1120.pdf",
        "source_locator": "Printed p. 14 Table 1; D1 green on",
        "source_editions": "MAN-070E: BOOK1120 REV 8, 2026/07/16",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Manaras-Opera",
        "control_platform": "BOARD 070E",
        "indicator_type": "LED pair",
        "code_or_pattern": "D2 and D3 both off",
        "what_the_operator_is_reporting": "DC power failure",
        "effect_on_the_door": "Door will not run",
        "what_to_report_or_have_assessed": "Report the indicator pair for qualified control-power assessment.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "MAN-070E",
        "source_urls": "https://manaras.com/book1120.pdf",
        "source_locator": "Printed p. 15 Table 2; D2 and D3 both off",
        "source_editions": "MAN-070E: BOOK1120 REV 8, 2026/07/16",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Manaras-Opera",
        "control_platform": "BOARD 070E",
        "indicator_type": "LED pair",
        "code_or_pattern": "D2 on, D3 flashing",
        "what_the_operator_is_reporting": "Wrong handing - a limit was not released within 3.6 seconds of starting travel",
        "effect_on_the_door": "External commands are ignored",
        "what_to_report_or_have_assessed": "Record the pair and any recent installation/electrical work. Do not change handing, limits or wiring.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "MAN-070E",
        "source_urls": "https://manaras.com/book1120.pdf",
        "source_locator": "Printed p. 15 Table 2; D2 on, D3 flashing",
        "source_editions": "MAN-070E: BOOK1120 REV 8, 2026/07/16",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Manaras-Opera",
        "control_platform": "BOARD 070E",
        "indicator_type": "LED pair",
        "code_or_pattern": "D2 and D3 both solid on",
        "what_the_operator_is_reporting": "Faulty motor centrifugal switch, single phase only",
        "effect_on_the_door": "Motor will not run correctly",
        "what_to_report_or_have_assessed": "Report the pair and single-phase model. The named component still needs the manual’s diagnostic process.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "MAN-070E",
        "source_urls": "https://manaras.com/book1120.pdf",
        "source_locator": "Printed p. 15 Table 2; D2 and D3 both solid on",
        "source_editions": "MAN-070E: BOOK1120 REV 8, 2026/07/16",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Manaras-Opera",
        "control_platform": "BOARD 070E",
        "indicator_type": "LED pair",
        "code_or_pattern": "D2 on, D3 off",
        "what_the_operator_is_reporting": "Standby",
        "effect_on_the_door": "Status indication only; it does not establish the whole installation is safe.",
        "what_to_report_or_have_assessed": "Record unexpected behaviour separately. This indication alone is not a fault diagnosis or a return-to-service decision.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "MAN-070E",
        "source_urls": "https://manaras.com/book1120.pdf",
        "source_locator": "Printed p. 15 Table 2; D2 on, D3 off",
        "source_editions": "MAN-070E: BOOK1120 REV 8, 2026/07/16",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Manaras-Opera",
        "control_platform": "BOARD 070E",
        "indicator_type": "LED pair",
        "code_or_pattern": "D2 flashing, D3 off",
        "what_the_operator_is_reporting": "Door opening",
        "effect_on_the_door": "Status indication only; it does not establish the whole installation is safe.",
        "what_to_report_or_have_assessed": "Record unexpected behaviour separately. This indication alone is not a fault diagnosis or a return-to-service decision.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "MAN-070E",
        "source_urls": "https://manaras.com/book1120.pdf",
        "source_locator": "Printed p. 15 Table 2; D2 flashing, D3 off",
        "source_editions": "MAN-070E: BOOK1120 REV 8, 2026/07/16",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Manaras-Opera",
        "control_platform": "BOARD 070E",
        "indicator_type": "LED pair",
        "code_or_pattern": "D2 off, D3 flashing",
        "what_the_operator_is_reporting": "Door closing",
        "effect_on_the_door": "Status indication only; it does not establish the whole installation is safe.",
        "what_to_report_or_have_assessed": "Record unexpected behaviour separately. This indication alone is not a fault diagnosis or a return-to-service decision.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "MAN-070E",
        "source_urls": "https://manaras.com/book1120.pdf",
        "source_locator": "Printed p. 15 Table 2; D2 off, D3 flashing",
        "source_editions": "MAN-070E: BOOK1120 REV 8, 2026/07/16",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Manaras-Opera",
        "control_platform": "BOARD 070E",
        "indicator_type": "LED pair",
        "code_or_pattern": "D2 and D3 both flashing",
        "what_the_operator_is_reporting": "Timer to close counting down, or a programming sequence in progress",
        "effect_on_the_door": "Meaning depends on timer/programming state; the pair alone does not prove that closing will occur.",
        "what_to_report_or_have_assessed": "Report whether a timed close or authorised programming was already in progress.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "MAN-070E",
        "source_urls": "https://manaras.com/book1120.pdf",
        "source_locator": "Printed p. 15 Table 2; D2 and D3 both flashing",
        "source_editions": "MAN-070E: BOOK1120 REV 8, 2026/07/16",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Manaras-Opera",
        "control_platform": "BOARD 070E",
        "indicator_type": "Status LED",
        "code_or_pattern": "D6 red on",
        "what_the_operator_is_reporting": "Reversing or sensing edge activated",
        "effect_on_the_door": "Response depends on the selected operating mode; it is not a universal powered-close lockout.",
        "what_to_report_or_have_assessed": "Report D6 and the installed sensing-device type. Response depends on mode.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "MAN-070E",
        "source_urls": "https://manaras.com/book1120.pdf",
        "source_locator": "Printed p. 14 Table 1; D6 red on",
        "source_editions": "MAN-070E: BOOK1120 REV 8, 2026/07/16",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Manaras-Opera",
        "control_platform": "BOARD 070E",
        "indicator_type": "Status LED",
        "code_or_pattern": "D9 yellow off",
        "what_the_operator_is_reporting": "Stop button not connected, or the hoist or disconnect switch is engaged",
        "effect_on_the_door": "Door will not respond",
        "what_to_report_or_have_assessed": "Report D9 and any known stop/hoist/disconnect condition. Do not bridge the circuit.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "MAN-070E",
        "source_urls": "https://manaras.com/book1120.pdf",
        "source_locator": "Printed p. 14 Table 1; D9 yellow off",
        "source_editions": "MAN-070E: BOOK1120 REV 8, 2026/07/16",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Manaras-Opera",
        "control_platform": "BOARD 070E",
        "indicator_type": "Status LED",
        "code_or_pattern": "D10 red on",
        "what_the_operator_is_reporting": "Inductive loop active",
        "effect_on_the_door": "Door can be closed only by constant pressure",
        "what_to_report_or_have_assessed": "Report the active loop indication and vehicle-presence history. Do not use held-button closing to bypass it.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "MAN-070E",
        "source_urls": "https://manaras.com/book1120.pdf",
        "source_locator": "Printed p. 14 Table 1; D10 red on",
        "source_editions": "MAN-070E: BOOK1120 REV 8, 2026/07/16",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Manaras-Opera",
        "control_platform": "BOARD 070E",
        "indicator_type": "Status LED",
        "code_or_pattern": "D12 / D13 / D14 red on",
        "what_the_operator_is_reporting": "Open limit, mid-stop limit or close limit reached",
        "effect_on_the_door": "A corresponding position input is active; interpret it with the selected mode.",
        "what_to_report_or_have_assessed": "Report the specific LED, not just that a red light is on.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "MAN-070E",
        "source_urls": "https://manaras.com/book1120.pdf",
        "source_locator": "Printed p. 14 Table 1; D12 / D13 / D14 red on",
        "source_editions": "MAN-070E: BOOK1120 REV 8, 2026/07/16",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL Medium, Standard, Heavy Duty and GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "3A  HALT > LOSS OF C/C",
        "what_the_operator_is_reporting": "Constant-contact input was released before the door reached a limit",
        "effect_on_the_door": "Door stopped, and may have reversed",
        "what_to_report_or_have_assessed": "Genie assigns no corrective action to this run code itself. Compare the already observed behaviour with the documented mode; do not use it as proof the whole door is healthy.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row 3A  HALT > LOSS OF C/C",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL / GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "3B  HALT > SHUTDOWN",
        "what_the_operator_is_reporting": "Hoist interlock or external interlock circuit opened, or the motor overheated",
        "effect_on_the_door": "Door stopped",
        "what_to_report_or_have_assessed": "Report the shutdown code and known hoist/interlock condition; overheating is another listed condition, not a confirmed diagnosis.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row 3B  HALT > SHUTDOWN",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL / GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "3E  HALT > MID STOP",
        "what_the_operator_is_reporting": "Door reached its programmed mid-stop position",
        "effect_on_the_door": "Travel stops there",
        "what_to_report_or_have_assessed": "Compare with the documented intended stop position; a newly changed position still needs assessment.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row 3E  HALT > MID STOP",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL / GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "39 / 49 / 59  DOOR FORCE",
        "what_the_operator_is_reporting": "The limit assembly slowed down, trolley models only",
        "effect_on_the_door": "Door stopped or reversed",
        "what_to_report_or_have_assessed": "Trolley models only: Genie begins with door balance. The force indication does not prove the motor has failed.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row 39 / 49 / 59  DOOR FORCE",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL / GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "46  REV > ODC STB",
        "what_the_operator_is_reporting": "Monitored safety beam or monitored edge activated while closing",
        "effect_on_the_door": "Door reversed to open",
        "what_to_report_or_have_assessed": "Report the active ODC STB input and installed device. Do not realign, disconnect or bypass it from this code alone.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row 46  REV > ODC STB",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL / GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "48  REV > MON. EDGE",
        "what_the_operator_is_reporting": "Monitored edge input on the timer module activated while closing",
        "effect_on_the_door": "Door reversed to open",
        "what_to_report_or_have_assessed": "Report the TCM monitored-edge input. The module, connected device and circuit need to be identified.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row 48  REV > MON. EDGE",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL / GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "4B  REV > MAX RUN TMR",
        "what_the_operator_is_reporting": "Maximum run time between limits exceeded while closing",
        "effect_on_the_door": "Door reversed",
        "what_to_report_or_have_assessed": "Genie begins its technician checks with door balance, then clutch/timer checks. Do not extend run time to mask resistance.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row 4B  REV > MAX RUN TMR",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL / GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "50  STOP > HOT MOTOR",
        "what_the_operator_is_reporting": "Motor overheated",
        "effect_on_the_door": "Door stopped",
        "what_to_report_or_have_assessed": "Report the hot-motor message and the preceding operating sequence; do not treat cooling as proof the problem is fixed.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row 50  STOP > HOT MOTOR",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL / GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "51 / 52  OPEN MRT / CLOSE MRT",
        "what_the_operator_is_reporting": "Maximum run time between limits exceeded",
        "effect_on_the_door": "Door stopped in that direction",
        "what_to_report_or_have_assessed": "Report the individual open/close timer code. Genie starts with door balance; no timer-adjustment instruction is given here.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row 51 / 52  OPEN MRT / CLOSE MRT",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL / GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "57  STOP > OPEN INTLK",
        "what_the_operator_is_reporting": "Hoist interlock or external interlock circuit opened",
        "effect_on_the_door": "Door stopped",
        "what_to_report_or_have_assessed": "Report the known hoist/interlock condition. Do not bypass the interlock to restore motion.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row 57  STOP > OPEN INTLK",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL / GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "58  STOP > WRONG GDO",
        "what_the_operator_is_reporting": "Operator type is configured as jackshaft but the hardware is identified as trolley",
        "effect_on_the_door": "Door stopped",
        "what_to_report_or_have_assessed": "Have the installed operator type and configuration checked against the hardware.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row 58  STOP > WRONG GDO",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL / GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "5A  STOP > WRONG LIMIT",
        "what_the_operator_is_reporting": "The unit expected one limit and the opposite limit became active",
        "effect_on_the_door": "Door stopped",
        "what_to_report_or_have_assessed": "Report the unexpected limit indication; qualified personnel must assess the limit configuration.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row 5A  STOP > WRONG LIMIT",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL / GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "5B  STOP > WRONG DIR",
        "what_the_operator_is_reporting": "Limit input arrived from the opposite direction to the one expected",
        "effect_on_the_door": "Door stopped",
        "what_to_report_or_have_assessed": "Report the direction/limit mismatch; no wiring or limit changes by the observer.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row 5B  STOP > WRONG DIR",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL / GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "5C / 5D / 5E  STALL",
        "what_the_operator_is_reporting": "The unit expected a limit to clear as the door moved off it, and never saw that signal",
        "effect_on_the_door": "Door stopped",
        "what_to_report_or_have_assessed": "Report the individual stall code. Genie begins with door balance; do not keep running a stalled door.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row 5C / 5D / 5E  STALL",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL / GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "60  CHECK STOP BTN",
        "what_the_operator_is_reporting": "The normally closed stop circuit is not complete",
        "effect_on_the_door": "Door will not move",
        "what_to_report_or_have_assessed": "Report the incomplete stop circuit and any known stop/hoist condition. Do not bridge it.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row 60  CHECK STOP BTN",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL / GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "61  TCM DISABLED",
        "what_the_operator_is_reporting": "No monitored sensing or safety device is enabled or working",
        "effect_on_the_door": "Door will not time out and close on its own",
        "what_to_report_or_have_assessed": "Have the installed monitored protection and timer configuration assessed; do not enable timed closing around a protection fault.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row 61  TCM DISABLED",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL / GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "62  NO RADIO >> C/C",
        "what_the_operator_is_reporting": "The unit is set to constant contact in the open and/or close mode, so radio commands are ignored",
        "effect_on_the_door": "Remotes do not work",
        "what_to_report_or_have_assessed": "Report code 62 and the intended operating arrangement; do not change to momentary operation without assessing protection and the installation.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row 62  NO RADIO >> C/C",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL / GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "64  CHECK STOP KEY",
        "what_the_operator_is_reporting": "The stop key on the circuit board is reading as active",
        "effect_on_the_door": "Unit will not run",
        "what_to_report_or_have_assessed": "Report the board STOP-key indication without opening the enclosure or forcing the key.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row 64  CHECK STOP KEY",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL / GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "66  CHECK ODC STB",
        "what_the_operator_is_reporting": "The ODC STB input on the main board is active; the connected device must be identified",
        "effect_on_the_door": "Unit will not close",
        "what_to_report_or_have_assessed": "Report code 66 and the actual connected protection device; the active input is not a component diagnosis.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row 66  CHECK ODC STB",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL / GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "68  CHECK MON. EDGE",
        "what_the_operator_is_reporting": "The monitored edge input on the timer module is reading as active",
        "effect_on_the_door": "Unit will not close",
        "what_to_report_or_have_assessed": "Report the TCM monitored-edge input and the connected device, if known from records.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row 68  CHECK MON. EDGE",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL / GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "69  OVERHEATED MOTOR",
        "what_the_operator_is_reporting": "Motor thermal overload is active",
        "effect_on_the_door": "Unit will not run",
        "what_to_report_or_have_assessed": "Report the thermal-overload message. Genie starts its technician checklist with door balance; the message alone is not an instruction to buy a motor.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row 69  OVERHEATED MOTOR",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL / GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "6C / 6D / 6E  NO RUN",
        "what_the_operator_is_reporting": "6C: close input while at down limit; 6D: open input while at up limit; 6E: active open input at or beyond mid-stop",
        "effect_on_the_door": "Requested movement is not made; the active input in 6E also prevents closing.",
        "what_to_report_or_have_assessed": "Report the individual code and already observed position; the mid-stop case is not an end-limit case.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row 6C / 6D / 6E  NO RUN",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL / GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "8C / 8D  SYSTEM VOLTS",
        "what_the_operator_is_reporting": "Secondary voltage too low, or line voltage too high for the unit's configuration",
        "effect_on_the_door": "Unit may not run",
        "what_to_report_or_have_assessed": "Record whether the message is 8C or 8D. Supply/configuration testing belongs to qualified electrical personnel.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row 8C / 8D  SYSTEM VOLTS",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL / GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "8E  REV INTERRUPTED",
        "what_the_operator_is_reporting": "A two-second reversal did not complete before the unit hit another problem and stopped",
        "effect_on_the_door": "Door stopped mid-reversal",
        "what_to_report_or_have_assessed": "Report the interrupted reversal and any subsequent message; do not recreate it.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row 8E  REV INTERRUPTED",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL / GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "A0 / A1 / A2  BTN BAD > PU",
        "what_the_operator_is_reporting": "A pushbutton input was already shorted when power was applied",
        "effect_on_the_door": "That input is ignored until it changes state",
        "what_to_report_or_have_assessed": "Report the individual input named at power-up; a shorted input needs qualified assessment.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row A0 / A1 / A2  BTN BAD > PU",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "GCL / GCX",
        "indicator_type": "Alphanumeric display",
        "code_or_pattern": "I2C Comm Error",
        "what_the_operator_is_reporting": "The board cannot communicate on its internal bus",
        "effect_on_the_door": "Unit may not run",
        "what_to_report_or_have_assessed": "Qualified assessment of the controller and connected modules. Do not unplug internal modules while energised.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Commercial Operator Run Codes / Error Codes, exact row I2C Comm Error",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "Fire Door Module",
        "indicator_type": "Trouble code blinks",
        "code_or_pattern": "1  CLUTCH FAULT",
        "what_the_operator_is_reporting": "Wiring from the fire door module to the electric clutch is broken or disconnected",
        "effect_on_the_door": "Fire Door Module trouble indication; the code alone does not verify the assembly’s operating condition.",
        "what_to_report_or_have_assessed": "Record the module model and complete trouble indication. Use trained rolling fire-door personnel; do not reset, test or rewire the assembly.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Printed p. 10, Fire Door Module trouble row 1  CLUTCH FAULT",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "Fire Door Module",
        "indicator_type": "Trouble code blinks",
        "code_or_pattern": "5 / 6 / 7  BATTERY",
        "what_the_operator_is_reporting": "Batteries are disconnected, not charging, or discharged",
        "effect_on_the_door": "Fire Door Module trouble indication; the code alone does not verify the assembly’s operating condition.",
        "what_to_report_or_have_assessed": "Record the module model and complete trouble indication. Use trained rolling fire-door personnel; do not reset, test or rewire the assembly.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Printed p. 10, Fire Door Module trouble row 5 / 6 / 7  BATTERY",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "Fire Door Module",
        "indicator_type": "Trouble code blinks",
        "code_or_pattern": "8  EXTERNAL POWER LOSS",
        "what_the_operator_is_reporting": "Primary input power to the fire door module is absent",
        "effect_on_the_door": "Fire Door Module trouble indication; the code alone does not verify the assembly’s operating condition.",
        "what_to_report_or_have_assessed": "Record the module model and complete trouble indication. Use trained rolling fire-door personnel; do not reset, test or rewire the assembly.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Printed p. 10, Fire Door Module trouble row 8  EXTERNAL POWER LOSS",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "Fire Door Module",
        "indicator_type": "Trouble code blinks",
        "code_or_pattern": "10 / 11  NOTIFICATION CIRCUIT",
        "what_the_operator_is_reporting": "Notification appliance wiring is open or short circuited",
        "effect_on_the_door": "Fire Door Module trouble indication; the code alone does not verify the assembly’s operating condition.",
        "what_to_report_or_have_assessed": "Record the module model and complete trouble indication. Use trained rolling fire-door personnel; do not reset, test or rewire the assembly.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Printed p. 10, Fire Door Module trouble row 10 / 11  NOTIFICATION CIRCUIT",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "Fire Door Module",
        "indicator_type": "Trouble code blinks",
        "code_or_pattern": "12  ALARM CIRCUIT OPEN",
        "what_the_operator_is_reporting": "Wiring to the smoke detector is broken, or the end-of-line device is not connected",
        "effect_on_the_door": "Fire Door Module trouble indication; the code alone does not verify the assembly’s operating condition.",
        "what_to_report_or_have_assessed": "Record the module model and complete trouble indication. Use trained rolling fire-door personnel; do not reset, test or rewire the assembly.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Printed p. 10, Fire Door Module trouble row 12  ALARM CIRCUIT OPEN",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "Fire Door Module",
        "indicator_type": "Trouble code blinks",
        "code_or_pattern": "15  TEST REQUIRED",
        "what_the_operator_is_reporting": "A test of the fire door and its operator is required",
        "effect_on_the_door": "Fire Door Module trouble indication; the code alone does not verify the assembly’s operating condition.",
        "what_to_report_or_have_assessed": "Record the module model and complete trouble indication. Use trained rolling fire-door personnel; do not reset, test or rewire the assembly.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Printed p. 10, Fire Door Module trouble row 15  TEST REQUIRED",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Genie",
        "control_platform": "Fire Door Module",
        "indicator_type": "Trouble code blinks",
        "code_or_pattern": "17  STUCK RESET",
        "what_the_operator_is_reporting": "The test and reset key switch is stuck in the reset position",
        "effect_on_the_door": "Fire Door Module trouble indication; the code alone does not verify the assembly’s operating condition.",
        "what_to_report_or_have_assessed": "Record the module model and complete trouble indication. Use trained rolling fire-door personnel; do not reset, test or rewire the assembly.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "Printed p. 10, Fire Door Module trouble row 17  STUCK RESET",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "brand": "Micanan",
        "control_platform": "PRO-J/PRO-H August 2010: relay logic with interface module, or Smart 10.0 in the specified modes",
        "indicator_type": "Documented behaviour (the Smart 10.0 also has status LEDs)",
        "code_or_pattern": "Fault mode",
        "what_the_operator_is_reporting": "In the specified momentary-close configurations, the primary monitored device is absent or not functioning",
        "effect_on_the_door": "Closes on constant pressure only; if the button is released before the door is fully closed, the door reverses to fully open",
        "what_to_report_or_have_assessed": "Report the installed controller and any behaviour already observed. E2 mode also reverses when released, so reversal alone does not diagnose a device fault.",
        "evidence_type": "Manufacturer-reported meaning; editorial handoff",
        "source_keys": "MIC-SMART",
        "source_urls": "https://ismartgate.com/manuals/Micanan_Pro-J_manual.pdf",
        "source_locator": "Printed p. 14 relay logic with interface module; p. 16 Smart 10.0 primary-device fault mode; p. 18 E2",
        "source_editions": "MIC-SMART: August 2010",
        "last_verified": "2026-09-17"
      }
    ],
    "constant-pressure-cause-tree": [
      {
        "branch": "1",
        "what_you_are_seeing": "It has worked this way since the door was installed",
        "documented_explanation": "Documented constant-pressure configuration is one possibility.",
        "what_this_does_not_establish": "Whether anything is broken, which part failed, or whether continued use is safe.",
        "safe_information_to_collect": "Record the documented mode and whether held-button closing has always been required.",
        "next_step": "Compare with the exact manual through trained, authorised personnel; do not bypass protection or change modes to hide a new fault.",
        "evidence_type": "Source-grounded interpretation; next step editorial",
        "source_keys": "DASMA382; LM-L5; MAN-070E; GENIE-TC; MIC-SMART",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2022/06/TDS382.pdf; https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf; https://manaras.com/book1120.pdf; https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf; https://ismartgate.com/manuals/Micanan_Pro-J_manual.pdf",
        "source_locator": "D382 pp. 1–2; LM pp. 28–29; MAN p. 16; GEN 62; MIC pp. 17–19",
        "source_editions": "DASMA382: REV 05/22/22 (orig 6/26/17); LM-L5: 45-page manufacturer manual; date not stated in inspected text; MAN-070E: BOOK1120 REV 8, 2026/07/16; GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2; MIC-SMART: August 2010",
        "last_verified": "2026-09-17"
      },
      {
        "branch": "2",
        "what_you_are_seeing": "It was hands-free until recently and now needs the button held",
        "documented_explanation": "A monitored-protection restriction is one possibility; a blockage is not necessarily a broken component.",
        "what_this_does_not_establish": "Whether anything is broken, which part failed, or whether continued use is safe.",
        "safe_information_to_collect": "Record the externally visible LMEP indication and any obstruction seen from outside the travel path.",
        "next_step": "Compare with the exact manual through trained, authorised personnel; do not bypass protection or change modes to hide a new fault.",
        "evidence_type": "Source-grounded interpretation; next step editorial",
        "source_keys": "LM-L5",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "LM p. 38 E7/p. 36 LMEP",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      },
      {
        "branch": "3",
        "what_you_are_seeing": "Closing starts a few seconds after the button is held, and stops the moment it is released",
        "documented_explanation": "LiftMaster E7 describes a delayed held-button override; elapsed time alone does not identify its cause.",
        "what_this_does_not_establish": "Whether anything is broken, which part failed, or whether continued use is safe.",
        "safe_information_to_collect": "Record a delay already observed; do not reproduce the delayed override.",
        "next_step": "Compare with the exact manual through trained, authorised personnel; do not bypass protection or change modes to hide a new fault.",
        "evidence_type": "Source-grounded interpretation; next step editorial",
        "source_keys": "LM-L5",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "LM p. 38 E7",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      },
      {
        "branch": "4",
        "what_you_are_seeing": "It needs the button held, and reverses to fully open if released early",
        "documented_explanation": "Specified Micanan fault-mode behaviour, or a configured E2 roll-back mode, can cause this pattern.",
        "what_this_does_not_establish": "Whether anything is broken, which part failed, or whether continued use is safe.",
        "safe_information_to_collect": "Identify the installed controller from records and report previously observed release behaviour.",
        "next_step": "Compare with the exact manual through trained, authorised personnel; do not bypass protection or change modes to hide a new fault.",
        "evidence_type": "Source-grounded interpretation; next step editorial",
        "source_keys": "MIC-SMART; LM-L5; MAN-070E",
        "source_urls": "https://ismartgate.com/manuals/Micanan_Pro-J_manual.pdf; https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf; https://manaras.com/book1120.pdf",
        "source_locator": "MIC pp. 14, 16, 18; LM/MAN E2 mode",
        "source_editions": "MIC-SMART: August 2010; LM-L5: 45-page manufacturer manual; date not stated in inspected text; MAN-070E: BOOK1120 REV 8, 2026/07/16",
        "last_verified": "2026-09-17"
      },
      {
        "branch": "5",
        "what_you_are_seeing": "It only responds to constant pressure after moving about a foot",
        "documented_explanation": "LiftMaster E2 error (two blinks, not E2 wiring mode) reports loss of opening motion feedback.",
        "what_this_does_not_establish": "Whether anything is broken, which part failed, or whether continued use is safe.",
        "safe_information_to_collect": "Record the two-blink maintenance indication; distinguish it from the E2 mode name.",
        "next_step": "Compare with the exact manual through trained, authorised personnel; do not bypass protection or change modes to hide a new fault.",
        "evidence_type": "Source-grounded interpretation; next step editorial",
        "source_keys": "LM-L5",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "LM p. 37 about-a-foot entry/p. 38 E2 error",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      },
      {
        "branch": "6",
        "what_you_are_seeing": "It ran normally for a few cycles, then dropped to constant pressure",
        "documented_explanation": "LiftMaster’s invalid-movement report can lead to held-button-only operation.",
        "what_this_does_not_establish": "Whether anything is broken, which part failed, or whether continued use is safe.",
        "safe_information_to_collect": "Record a flash already observed at movement start; do not run additional cycles to create it.",
        "next_step": "Compare with the exact manual through trained, authorised personnel; do not bypass protection or change modes to hide a new fault.",
        "evidence_type": "Source-grounded interpretation; next step editorial",
        "source_keys": "LM-L5",
        "source_urls": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "LM p. 38 E9",
        "source_editions": "LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      },
      {
        "branch": "7",
        "what_you_are_seeing": "Constant pressure is needed only when a vehicle is near the door",
        "documented_explanation": "Manaras D10 indicates an active loop input and the manual describes held-button closing while active.",
        "what_this_does_not_establish": "Whether anything is broken, which part failed, or whether continued use is safe.",
        "safe_information_to_collect": "Record an already accessible D10 indication and vehicle-presence history.",
        "next_step": "Compare with the exact manual through trained, authorised personnel; do not bypass protection or change modes to hide a new fault.",
        "evidence_type": "Source-grounded interpretation; next step editorial",
        "source_keys": "MAN-070E",
        "source_urls": "https://manaras.com/book1120.pdf",
        "source_locator": "MAN p. 14 Table 1 D10",
        "source_editions": "MAN-070E: BOOK1120 REV 8, 2026/07/16",
        "last_verified": "2026-09-17"
      },
      {
        "branch": "8",
        "what_you_are_seeing": "The remote has stopped working, and the wall button only closes when held",
        "documented_explanation": "Genie code 62 reports constant-contact configuration disabling radio input.",
        "what_this_does_not_establish": "Whether anything is broken, which part failed, or whether continued use is safe.",
        "safe_information_to_collect": "Record code 62 and whether the remote previously worked.",
        "next_step": "Compare with the exact manual through trained, authorised personnel; do not bypass protection or change modes to hide a new fault.",
        "evidence_type": "Source-grounded interpretation; next step editorial",
        "source_keys": "GENIE-TC",
        "source_urls": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "source_locator": "GEN p. 5 code 62",
        "source_editions": "GENIE-TC: 10-page document; publication date not stated; file metadata identifies v2",
        "last_verified": "2026-09-17"
      },
      {
        "branch": "9",
        "what_you_are_seeing": "No entrapment device has ever been fitted to this door",
        "documented_explanation": "The installed configuration and learned protection need verification; absent protection is not permission to alter it.",
        "what_this_does_not_establish": "Whether anything is broken, which part failed, or whether continued use is safe.",
        "safe_information_to_collect": "Use installation/service records to identify protection; a dark LED is not its installation history.",
        "next_step": "Compare with the exact manual through trained, authorised personnel; do not bypass protection or change modes to hide a new fault.",
        "evidence_type": "Source-grounded interpretation; next step editorial",
        "source_keys": "DASMA382; LM-L5",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2022/06/TDS382.pdf; https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "source_locator": "D382 pp. 1–2; LM p. 36 LMEP status/p. 39 radio R6",
        "source_editions": "DASMA382: REV 05/22/22 (orig 6/26/17); LM-L5: 45-page manufacturer manual; date not stated in inspected text",
        "last_verified": "2026-09-17"
      }
    ],
    "name-crosswalk": [
      {
        "what_people_call_it": "The rubber strip at the bottom",
        "industry_term": "Astragal",
        "door_type": "Sectional; Rolling steel",
        "why_the_right_word_matters": "It is a seal. It is not the same component as a sensing edge.",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA277; DASMA160",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf; https://www.dasma.com/wp-content/uploads/2020/06/TDS160-Sectional-Garage-Door-Terminology.pdf",
        "source_locator": "Named terminology entry: Astragal",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20; DASMA160: Rev 8/17 Reaff 6/18 Rev 1/19",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The rubber strip that stops the door",
        "industry_term": "Sensing edge",
        "door_type": "Sectional; Rolling steel",
        "why_the_right_word_matters": "It is a safety device, not weatherstripping.",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA277",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf",
        "source_locator": "Named terminology entry: Sensing edge",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The electric eyes",
        "industry_term": "Photoelectric sensor",
        "door_type": "All powered",
        "why_the_right_word_matters": "Names the sensor type; replacement compatibility still depends on the installed system.",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA382",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2022/06/TDS382.pdf",
        "source_locator": "Named terminology entry: Photoelectric sensor",
        "source_editions": "DASMA382: REV 05/22/22 (orig 6/26/17)",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The big roll at the top",
        "industry_term": "Barrel assembly",
        "door_type": "Rolling steel; Grille",
        "why_the_right_word_matters": "A shaft/barrel assembly that supports the curtain and may contain the counterbalance; its name does not diagnose a spring fault.",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA277",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf",
        "source_locator": "Named terminology entry: Barrel assembly",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The metal cover over the roll",
        "industry_term": "Hood",
        "door_type": "Rolling steel; Grille",
        "why_the_right_word_matters": "Distinct from the fascia and the access panel",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA277",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf",
        "source_locator": "Named terminology entry: Hood",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The side channels",
        "industry_term": "Guides",
        "door_type": "Rolling steel; Grille",
        "why_the_right_word_matters": "Sectional doors have tracks. Rolling doors have guides.",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA277",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf",
        "source_locator": "Named terminology entry: Guides",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The rails",
        "industry_term": "Track",
        "door_type": "Sectional",
        "why_the_right_word_matters": "Vertical, horizontal, high lift and low headroom all need different parts",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA160",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2020/06/TDS160-Sectional-Garage-Door-Terminology.pdf",
        "source_locator": "Named terminology entry: Track",
        "source_editions": "DASMA160: Rev 8/17 Reaff 6/18 Rev 1/19",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The flared part at the top of the channel",
        "industry_term": "Bellmouth",
        "door_type": "Rolling steel; Grille",
        "why_the_right_word_matters": "The flared guide entrance. Naming it identifies where damage was observed, not the cause of every jam.",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA277",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf",
        "source_locator": "Named terminology entry: Bellmouth",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The little clips on the slat ends",
        "industry_term": "Endlocks",
        "door_type": "Rolling steel",
        "why_the_right_word_matters": "Endlocks restrain sideways slat movement; the complete curtain still needs inspection.",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA277",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf",
        "source_locator": "Named terminology entry: Endlocks",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The bar at the bottom of a roll-up",
        "industry_term": "Bottom bar",
        "door_type": "Rolling steel; Grille",
        "why_the_right_word_matters": "Where the sensing edge and the locks live",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA277",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf",
        "source_locator": "Named terminology entry: Bottom bar",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The wheel on the side",
        "industry_term": "Tension wheel, also charge wheel or adjusting wheel",
        "door_type": "Rolling steel",
        "why_the_right_word_matters": "Under spring load. Adjustment requires trained, authorised personnel and the equipment-specific procedure.",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA277",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf",
        "source_locator": "Named terminology entry: Tension wheel, also charge wheel or adjusting wheel",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The pin holding the tension",
        "industry_term": "Charge pin",
        "door_type": "Rolling steel",
        "why_the_right_word_matters": "Locks the tension wheel once spring tension is applied",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA277",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf",
        "source_locator": "Named terminology entry: Charge pin",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The chain you pull to work it by hand",
        "industry_term": "Chain hoist",
        "door_type": "Rolling steel; Grille; Sectional",
        "why_the_right_word_matters": "Different from an emergency release device",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA277; DASMA160",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf; https://www.dasma.com/wp-content/uploads/2020/06/TDS160-Sectional-Garage-Door-Terminology.pdf",
        "source_locator": "Named terminology entry: Chain hoist",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20; DASMA160: Rev 8/17 Reaff 6/18 Rev 1/19",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The rope or handle that disconnects the motor",
        "industry_term": "Emergency release device",
        "door_type": "Sectional; Rolling steel",
        "why_the_right_word_matters": "Allows manual operation without power",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA277",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf",
        "source_locator": "Named terminology entry: Emergency release device",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The chain that unhooks the operator",
        "industry_term": "Disconnect chain",
        "door_type": "Sectional, industrial operators",
        "why_the_right_word_matters": "Lets the hand chain work the door in a power failure",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA160",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2020/06/TDS160-Sectional-Garage-Door-Terminology.pdf",
        "source_locator": "Named terminology entry: Disconnect chain",
        "source_editions": "DASMA160: Rev 8/17 Reaff 6/18 Rev 1/19",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The thing that stops it dropping if a spring goes",
        "industry_term": "Inertia brake, also safety stop bearing or stop lock bearing",
        "door_type": "Rolling steel",
        "why_the_right_word_matters": "A device intended to stop free fall; an engaged brake needs equipment-specific assessment, not an improvised reset.",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA277",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf",
        "source_locator": "Named terminology entry: Inertia brake, also safety stop bearing or stop lock bearing",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The bracket that stops the door falling if a cable snaps",
        "industry_term": "Broken cable device or cable safety device",
        "door_type": "Sectional",
        "why_the_right_word_matters": "A bottom fixture meant to stop or slow a falling door",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA160",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2020/06/TDS160-Sectional-Garage-Door-Terminology.pdf",
        "source_locator": "Named terminology entry: Broken cable device or cable safety device",
        "source_editions": "DASMA160: Rev 8/17 Reaff 6/18 Rev 1/19",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The wire inside the side spring",
        "industry_term": "Containment cable",
        "door_type": "Sectional",
        "why_the_right_word_matters": "Retains an extension spring if it breaks",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA160",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2020/06/TDS160-Sectional-Garage-Door-Terminology.pdf",
        "source_locator": "Named terminology entry: Containment cable",
        "source_editions": "DASMA160: Rev 8/17 Reaff 6/18 Rev 1/19",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The bar across the door",
        "industry_term": "Strut",
        "door_type": "Sectional",
        "why_the_right_word_matters": "Stiffens the door section; a wind rating belongs to the specified complete door assembly, not the word strut alone.",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA160",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2020/06/TDS160-Sectional-Garage-Door-Terminology.pdf",
        "source_locator": "Named terminology entry: Strut",
        "source_editions": "DASMA160: Rev 8/17 Reaff 6/18 Rev 1/19",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The vertical pieces on the section edges",
        "industry_term": "End stile and center stile",
        "door_type": "Sectional",
        "why_the_right_word_matters": "Where hinges and rollers attach",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA160",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2020/06/TDS160-Sectional-Garage-Door-Terminology.pdf",
        "source_locator": "Named terminology entry: End stile and center stile",
        "source_editions": "DASMA160: Rev 8/17 Reaff 6/18 Rev 1/19",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The corner bracket at the bottom",
        "industry_term": "Bottom bracket",
        "door_type": "Sectional",
        "why_the_right_word_matters": "Connected to lifting hardware under high spring tension. Do not loosen or adjust it.",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA160",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2020/06/TDS160-Sectional-Garage-Door-Terminology.pdf",
        "source_locator": "Named terminology entry: Bottom bracket",
        "source_editions": "DASMA160: Rev 8/17 Reaff 6/18 Rev 1/19",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The round drum the cable winds on",
        "industry_term": "Cable drum",
        "door_type": "Sectional",
        "why_the_right_word_matters": "A grooved drum for the lifting cable; crooked travel alone does not diagnose drum slip.",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA160",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2020/06/TDS160-Sectional-Garage-Door-Terminology.pdf",
        "source_locator": "Named terminology entry: Cable drum",
        "source_editions": "DASMA160: Rev 8/17 Reaff 6/18 Rev 1/19",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The cable",
        "industry_term": "Aircraft-type cable, or lifting cable",
        "door_type": "Sectional",
        "why_the_right_word_matters": "DASMA #160 defines aircraft-type cable as braided strands of galvanized wire rope. Identify the specified replacement rather than selecting it by this name alone.",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA160",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2020/06/TDS160-Sectional-Garage-Door-Terminology.pdf",
        "source_locator": "Named terminology entry: Aircraft-type cable, or lifting cable",
        "source_editions": "DASMA160: Rev 8/17 Reaff 6/18 Rev 1/19",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The spring above the door",
        "industry_term": "Torsion spring",
        "door_type": "Sectional; Rolling steel",
        "why_the_right_word_matters": "Stored energy. Trained technicians only.",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA160; DASMA277",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2020/06/TDS160-Sectional-Garage-Door-Terminology.pdf; https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf",
        "source_locator": "Named terminology entry: Torsion spring",
        "source_editions": "DASMA160: Rev 8/17 Reaff 6/18 Rev 1/19; DASMA277: 9/3/03 Rev 6/20",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The springs along the side rails",
        "industry_term": "Extension spring",
        "door_type": "Sectional",
        "why_the_right_word_matters": "A different counterbalance and a different repair",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA160",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2020/06/TDS160-Sectional-Garage-Door-Terminology.pdf",
        "source_locator": "Named terminology entry: Extension spring",
        "source_editions": "DASMA160: Rev 8/17 Reaff 6/18 Rev 1/19",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The cone on the end of the spring",
        "industry_term": "Winding cone and stationary cone",
        "door_type": "Sectional",
        "why_the_right_word_matters": "Where spring tension is set and released",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA160",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2020/06/TDS160-Sectional-Garage-Door-Terminology.pdf",
        "source_locator": "Named terminology entry: Winding cone and stationary cone",
        "source_editions": "DASMA160: Rev 8/17 Reaff 6/18 Rev 1/19",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The bar they stick in the spring",
        "industry_term": "Winding rod, also winding bar",
        "door_type": "Sectional",
        "why_the_right_word_matters": "The tool that makes spring work possible, and dangerous",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA160",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2020/06/TDS160-Sectional-Garage-Door-Terminology.pdf",
        "source_locator": "Named terminology entry: Winding rod, also winding bar",
        "source_editions": "DASMA160: Rev 8/17 Reaff 6/18 Rev 1/19",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The hooks in the guide with a bar behind them",
        "industry_term": "Windlock and wind bar",
        "door_type": "Rolling steel",
        "why_the_right_word_matters": "Keeps the curtain in the guides under wind load",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA277",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf",
        "source_locator": "Named terminology entry: Windlock and wind bar",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The lock that stops the motor",
        "industry_term": "External interlock, or electrical interlock",
        "door_type": "All powered",
        "why_the_right_word_matters": "Prevents operation when its associated lock or device is engaged; it is not hazardous-energy isolation.",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA277; DASMA160",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf; https://www.dasma.com/wp-content/uploads/2020/06/TDS160-Sectional-Garage-Door-Terminology.pdf",
        "source_locator": "Named terminology entry: External interlock, or electrical interlock",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20; DASMA160: Rev 8/17 Reaff 6/18 Rev 1/19",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The little door in the big door",
        "industry_term": "Pass door, also wicket door",
        "door_type": "Rolling steel; Sectional",
        "why_the_right_word_matters": "A pedestrian door within the larger door; an associated interlock can affect operation. This label does not establish exit-code compliance.",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA277; DASMA160",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf; https://www.dasma.com/wp-content/uploads/2020/06/TDS160-Sectional-Garage-Door-Terminology.pdf",
        "source_locator": "Named terminology entry: Pass door, also wicket door",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20; DASMA160: Rev 8/17 Reaff 6/18 Rev 1/19",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The guard in front of the track",
        "industry_term": "Track guard",
        "door_type": "Sectional",
        "why_the_right_word_matters": "Protects the track against impact; the definition is not an installation mandate.",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA160",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2020/06/TDS160-Sectional-Garage-Door-Terminology.pdf",
        "source_locator": "Named terminology entry: Track guard",
        "source_editions": "DASMA160: Rev 8/17 Reaff 6/18 Rev 1/19",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The springs on the horizontal track",
        "industry_term": "Push down spring",
        "door_type": "Sectional",
        "why_the_right_word_matters": "Helps start the door down and keeps cable tension, typically with a jackshaft operator or hand chain",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA160",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2020/06/TDS160-Sectional-Garage-Door-Terminology.pdf",
        "source_locator": "Named terminology entry: Push down spring",
        "source_editions": "DASMA160: Rev 8/17 Reaff 6/18 Rev 1/19",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The slope on the overhead rails",
        "industry_term": "Horizontal rise",
        "door_type": "Sectional",
        "why_the_right_word_matters": "The upward slope that helps start the door down and maintain cable tension",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA160",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2020/06/TDS160-Sectional-Garage-Door-Terminology.pdf",
        "source_locator": "Named terminology entry: Horizontal rise",
        "source_editions": "DASMA160: Rev 8/17 Reaff 6/18 Rev 1/19",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "It will not stay up",
        "industry_term": "Dead in the head",
        "door_type": "Sectional",
        "why_the_right_word_matters": "The trade term for no counterbalance at the open position",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA160",
        "source_urls": "https://www.dasma.com/wp-content/uploads/2020/06/TDS160-Sectional-Garage-Door-Terminology.pdf",
        "source_locator": "Named terminology entry: Dead in the head",
        "source_editions": "DASMA160: Rev 8/17 Reaff 6/18 Rev 1/19",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The small metal link on a chain with a weight",
        "industry_term": "Fusible link",
        "door_type": "Rolling fire door",
        "why_the_right_word_matters": "A heat-responsive link associated with release hardware. Confirm the door from labels and records rather than from the link alone.",
        "fire_door_only_term": "YES",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA277",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf",
        "source_locator": "Named terminology entry: Fusible link",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The weight that drops the door",
        "industry_term": "Dropout",
        "door_type": "Rolling fire door",
        "why_the_right_word_matters": "Disengages the gearing or operator so the door can close in a fire",
        "fire_door_only_term": "YES",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA277",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf",
        "source_locator": "Named terminology entry: Dropout",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The thing that slows the door as it drops",
        "industry_term": "Governor",
        "door_type": "Rolling door; verify installed application",
        "why_the_right_word_matters": "Controls descent speed; DASMA #277 does not mark Governor with its fire-only asterisk.",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA277",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf",
        "source_locator": "Named terminology entry: Governor",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The flap inside the hood",
        "industry_term": "Flame baffle",
        "door_type": "Rolling fire door",
        "why_the_right_word_matters": "Closes the gap between curtain and hood when released",
        "fire_door_only_term": "YES",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA277",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf",
        "source_locator": "Named terminology entry: Flame baffle",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The box that drops the door on the alarm",
        "industry_term": "Automatic closing device, electromechanical release, or magnetic release",
        "door_type": "Rolling fire door",
        "why_the_right_word_matters": "Triggered by a fusible link, a detector, or an alarm signal",
        "fire_door_only_term": "YES",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA277",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf",
        "source_locator": "Named terminology entry: Automatic closing device, electromechanical release, or magnetic release",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "The yearly test",
        "industry_term": "Drop test",
        "door_type": "Rolling fire door",
        "why_the_right_word_matters": "A fire-door operating test. See DASMA #299’s NFPA 80-2022 explanation and the locally applicable requirements.",
        "fire_door_only_term": "YES",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA277; DASMA299",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf; https://www.dasma.com/wp-content/uploads/2023/04/TDS299.pdf",
        "source_locator": "Named terminology entry: Drop test; DASMA #299 pp. 1–2 for periodic testing context",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20; DASMA299: 4/13/23; discusses NFPA 80-2022",
        "last_verified": "2026-09-17"
      },
      {
        "what_people_call_it": "One trip up and down",
        "industry_term": "Cycle",
        "door_type": "All",
        "why_the_right_word_matters": "Fully closed, to fully open, and back to fully closed. A controller’s counting convention still needs its own manual.",
        "fire_door_only_term": "No",
        "evidence_type": "Source-defined term; practical explanation editorial",
        "source_keys": "DASMA277; DASMA160",
        "source_urls": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf; https://www.dasma.com/wp-content/uploads/2020/06/TDS160-Sectional-Garage-Door-Terminology.pdf",
        "source_locator": "Named terminology entry: Cycle",
        "source_editions": "DASMA277: 9/3/03 Rev 6/20; DASMA160: Rev 8/17 Reaff 6/18 Rev 1/19",
        "last_verified": "2026-09-17"
      }
    ],
    "sources": [
      {
        "source_key": "DASMA382",
        "publisher": "DASMA",
        "title": "TDS #382 Proper Installation of Photoelectric Non-Contact Sensors on Vehicular Commercial Door Operators",
        "edition_or_revision": "REV 05/22/22 (orig 6/26/17)",
        "url": "https://www.dasma.com/wp-content/uploads/2022/06/TDS382.pdf",
        "date_read": "2026-09-17",
        "verification_level": "Relevant primary-source text checked",
        "used_sections": "pp. 1–2 commercial vehicular operator scope, monitored devices, beam height, Testing"
      },
      {
        "source_key": "DASMA375",
        "publisher": "DASMA",
        "title": "TDS #375 Motor Operated Commercial Sectional Doors and Rolling Doors: Typical Installation Concerns",
        "edition_or_revision": "2/8/06 Rev 12-13 Reaff 3-17",
        "url": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/OperatorElectronics/TDS375.pdf",
        "date_read": "2026-09-17",
        "verification_level": "Relevant primary-source text checked",
        "used_sections": "pp. 1–2 typical installation concerns; reversing device/closing direction"
      },
      {
        "source_key": "DASMA277",
        "publisher": "DASMA",
        "title": "TDS #277 Rolling Door Terminology",
        "edition_or_revision": "9/3/03 Rev 6/20",
        "url": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/RollingDoor/TDS277.pdf",
        "date_read": "2026-09-17",
        "verification_level": "Relevant primary-source text checked",
        "used_sections": "Named terminology entries; asterisk convention; not evidence of symptom frequency"
      },
      {
        "source_key": "DASMA358",
        "publisher": "DASMA",
        "title": "TDS #358 Vehicular Commercial Door and Gate Operators, and OSHA Requirements",
        "edition_or_revision": "12/20/02 Rev 1/14 Rev 10/15",
        "url": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/OperatorElectronics/TDS358.pdf",
        "date_read": "2026-09-17",
        "verification_level": "Relevant primary-source text checked",
        "used_sections": "p. 1 OSHA approval discussion; historical industry explanation, not a current UL clause"
      },
      {
        "source_key": "DASMA160",
        "publisher": "DASMA",
        "title": "TDS #160 Sectional Garage Door Terminology",
        "edition_or_revision": "Rev 8/17 Reaff 6/18 Rev 1/19",
        "url": "https://www.dasma.com/wp-content/uploads/2020/06/TDS160-Sectional-Garage-Door-Terminology.pdf",
        "date_read": "2026-09-17",
        "verification_level": "Relevant primary-source text checked",
        "used_sections": "Named terminology entries; not evidence of symptom frequency"
      },
      {
        "source_key": "DASMA1501",
        "publisher": "DASMA",
        "title": "TDS #1501 Standard Lift Garage Doors with Jackshaft Operation",
        "edition_or_revision": "12/08/22",
        "url": "https://www.dasma.com/wp-content/uploads/2022/12/TDS1501.pdf",
        "date_read": "2026-09-17",
        "verification_level": "Relevant primary-source text checked",
        "used_sections": "pp. 1–3 standard-lift jackshaft application and cable tension"
      },
      {
        "source_key": "LM-L5",
        "publisher": "LiftMaster (Chamberlain Group)",
        "title": "Logic 5.0 Installation Manual — T, APT, H, J, HJ, GH, GT",
        "edition_or_revision": "45-page manufacturer manual; date not stated in inspected text",
        "url": "https://www.devancocanada.com/files/manuals/H105L5:Logic-5-Installation-Manual.pdf",
        "date_read": "2026-09-17",
        "verification_level": "Relevant primary-source text checked",
        "used_sections": "Printed pp. 28–29 wiring types; pp. 34–35 timer/counter; pp. 36–39 diagnostics; manufacturer-authored PDF hosted by Devanco"
      },
      {
        "source_key": "MAN-070E",
        "publisher": "Manaras-Opera",
        "title": "Installation & Instruction Manual, Electronic Control BOARD 070E",
        "edition_or_revision": "BOOK1120 REV 8, 2026/07/16",
        "url": "https://manaras.com/book1120.pdf",
        "date_read": "2026-09-17",
        "verification_level": "Relevant primary-source text checked",
        "used_sections": "Printed p. 6 §1.4 photo cells; pp. 14–15 Tables 1–2; p. 16 modes; p. 17 maximum run timer; p. 18 cycle counter"
      },
      {
        "source_key": "GENIE-TC",
        "publisher": "The Genie Company",
        "title": "Commercial Operator Troubleshooting Codes — GCL Medium, Standard, Heavy Duty and GCX",
        "edition_or_revision": "10-page document; publication date not stated; file metadata identifies v2",
        "url": "https://3ef5a44a-92ea-43d8-b1f7-c357f8ce6381.usrfiles.com/ugd/3ef5a4_ce58a6a75d6c441dafa9ce6e633ade88.pdf",
        "date_read": "2026-09-17",
        "verification_level": "Relevant primary-source text checked",
        "used_sections": "pp. 1–3 run codes; pp. 3–9 error codes; p. 10 Fire Door Module; linked by Genie commercial-document library"
      },
      {
        "source_key": "MIC-SMART",
        "publisher": "Micanan Systems",
        "title": "PRO-J / PRO-H Installation and Instruction Manual — Smart 10.0 and relay logic with interface module",
        "edition_or_revision": "August 2010",
        "url": "https://ismartgate.com/manuals/Micanan_Pro-J_manual.pdf",
        "date_read": "2026-09-17",
        "verification_level": "Relevant primary-source text checked",
        "used_sections": "Printed pp. 4–5 safety; p. 14 interface-module fault mode; pp. 16–23 Smart 10.0; manufacturer-authored PDF hosted by ismartgate"
      },
      {
        "source_key": "OSHA147",
        "publisher": "US OSHA",
        "title": "29 CFR 1910.147 — Control of hazardous energy",
        "edition_or_revision": "Federal rule text checked 2026-09-17",
        "url": "https://www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.147",
        "date_read": "2026-09-17",
        "verification_level": "Relevant primary-source text checked",
        "used_sections": "1910.147(a)(1)(i), (a)(1)(ii), (b) energy-isolating-device definition, (c), (d)(5) stored energy"
      },
      {
        "source_key": "OSHA333",
        "publisher": "US OSHA",
        "title": "29 CFR 1910.333 — Selection and use of work practices",
        "edition_or_revision": "Federal rule text checked 2026-09-17",
        "url": "https://www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.333",
        "date_read": "2026-09-17",
        "verification_level": "Relevant primary-source text checked",
        "used_sections": "1910.333(b)(2)(ii)(B), (b)(2)(iv), (c)(2)"
      },
      {
        "source_key": "OSHA399",
        "publisher": "US OSHA",
        "title": "29 CFR 1910.399 — Definitions applicable to electrical rules",
        "edition_or_revision": "Federal rule text checked 2026-09-17",
        "url": "https://www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.399",
        "date_read": "2026-09-17",
        "verification_level": "Relevant primary-source text checked",
        "used_sections": "Definitions: Acceptable; Approved; Qualified person"
      },
      {
        "source_key": "OSHA303",
        "publisher": "US OSHA",
        "title": "29 CFR 1910.303 — General electrical requirements",
        "edition_or_revision": "Federal rule text checked 2026-09-17",
        "url": "https://www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.303",
        "date_read": "2026-09-17",
        "verification_level": "Relevant primary-source text checked",
        "used_sections": "1910.303(a) approval; (b)(2) listed/labeled equipment instructions"
      },
      {
        "source_key": "DASMA269",
        "publisher": "DASMA",
        "title": "TDS #269 Rolling Door and Rolling Fire Door Visual Inspection",
        "edition_or_revision": "Rev 2/21; issued 3/15/21",
        "url": "https://www.dasma.com/wp-content/uploads/2021/03/TDS269-l.pdf",
        "date_read": "2026-09-17",
        "verification_level": "Relevant primary-source text checked",
        "used_sections": "pp. 1–3 scope, warning, hood/guides/curtain/bottom bar, sensing-edge procedure, performance criteria"
      },
      {
        "source_key": "DASMA176",
        "publisher": "DASMA",
        "title": "TDS #176 Adding Weight to a Sectional Garage Door",
        "edition_or_revision": "1/30/06; Rev 8/08; reaffirmed 6/19",
        "url": "https://www.dasma.com/wp-content/uploads/pubs/TechDataSheets/CommercialResidential/TDS176.pdf",
        "date_read": "2026-09-17",
        "verification_level": "Relevant primary-source text checked",
        "used_sections": "p. 1 added weight, counterbalance and operator effects"
      },
      {
        "source_key": "DASMA299",
        "publisher": "DASMA",
        "title": "TDS #299 Rolling Steel Fire Door Periodic Inspection and Technician Training Requirements",
        "edition_or_revision": "4/13/23; discusses NFPA 80-2022",
        "url": "https://www.dasma.com/wp-content/uploads/2023/04/TDS299.pdf",
        "date_read": "2026-09-17",
        "verification_level": "Relevant primary-source text checked",
        "used_sections": "pp. 1–2; DASMA explanation of NFPA 80-2022 §§5.2.4.2 and 3.3.131; not the standard itself"
      },
      {
        "source_key": "DASMA252",
        "publisher": "DASMA",
        "title": "TDS #252 Test Rolling Fire Doors in the Fully Open Position ONLY",
        "edition_or_revision": "Rev 8/24",
        "url": "https://www.dasma.com/wp-content/uploads/2025/01/TDS-252.pdf",
        "date_read": "2026-09-17",
        "verification_level": "Relevant primary-source text checked",
        "used_sections": "p. 1 design-dependent drop-test precautions"
      },
      {
        "source_key": "DASMA267",
        "publisher": "DASMA",
        "title": "TDS #267 Rolling Door Product Safety Label Recommendations",
        "edition_or_revision": "Rev 1/24",
        "url": "https://www.dasma.com/wp-content/uploads/2025/04/TDS267.pdf",
        "date_read": "2026-09-17",
        "verification_level": "Relevant primary-source text checked",
        "used_sections": "RDD-200, RDD-203 and RDD-205 label recommendations; fire-door identification and test records"
      },
      {
        "source_key": "CLOPAY",
        "publisher": "Clopay",
        "title": "Commercial Door Maintenance",
        "edition_or_revision": "Undated web page; checked 2026-09-17",
        "url": "https://www.clopaydoor.com/commercial-door-maintenance",
        "date_read": "2026-09-17",
        "verification_level": "Relevant primary-source text checked",
        "used_sections": "Warnings; Inspection; Check Operation"
      }
    ]
  }
}